3) Operating Environment
Temperature
Humidity
Altitude
Storage temperature
0
°
C-45
°
C
<95%
<1000m
-15
°
C-50
°
C
Note: if the UPS is installed or used in a place where the altitude is
above than
1000m
, the output power must be derated in use, please
refer to the following:
Altitude (M)
1000 1500 2000 2500 3000 3500 4000 4500 5000
Maximum
Power
100% 95% 91% 86% 82% 78% 74% 70% 67%
13
4. Installation
The system may be installed and wired only by qualified
electricians in accordance with applicable safety regulations!
4.1 Unpacking and Inspection
1. Moving to the installation site
The tower 3-phase series UPS has wheels making it easy to move the
UPS to the installation site after it has been unpacked. However, if the
receiving area is far from the installation site, we recommend you to
move the UPS by using a pallet jack or a lifter before you start to
unpack the UPS.
2. Unpacking and inspection
1) At the installation site, the utmost care shall be taken when
removing the packaging in order to avoid damaging the equipment.
Check all packaging materials to ensure that no items are missing.
The shipping package contains:
●
A UPS
●
A user manual
●
A communication cable
●
Parallel port cover plate