13
ZY120 1-3kVA User Manual EN rev.08.docx
Output
Voltage
200V/208V/220V/230V/240V
Current
5/4.8/4.5/4.3/4.2A
10/9.6/9/8.6/8.4A
15/14.4/13.5/12.9/12.
6A
Dimension
(WxDxH) mm
144*353*222
190*374*336
190*426*336
Weight (kg)
6
12
10
21
11
26
Factory setting 230Vac-50Hz
2. Electrical Performance
Input
Model
Voltage
Frequency
Power Factor
1-3KVA
Single-phase
40-70Hz
>0.98(Full load)
3. Operating Environment
Temperature
Humidity
Altitude
Storage temperature
0
C-40
C
<95%
<1000m
-20
C-70
C
NOTICE
:
If the UPS is installed or used in a place where the altitude is above than
1000m
,
the output power must be derated in use, please refer to the following:
Altitude (M)
1000
1500
2000
2500
3000
3500
4000
4500
5000
Derating Power
100%
95%
91%
86%
82%
78%
74%
70%
67%
Output
Voltage
Regulation
Power
Factor
Frequency
tolerance.
Distortion
Overload capacity
Crest ratio
1%
0.9 lag
0.5% of
normal
THD<1%@Fu
ll Linear Load
THD<6%@Fu
ll nonlinear
load
130% load: transfers to
Bypass mode after 1
minutes
150% load: transfers to
Bypass mode after 0.5
minute
3:1
maximum