Chimneys
The size and height all depend on the unit you have purchased and where the unit will be located. If the furnace is located within 300
feet of any residence, then the chimney stack must be at least two (2) feet higher than the peak of the tallest roof. It is recommended
that only a double insulated, stainless steel, Class A chimney pipe to be used. Contact your local dealer or Greentech Manufacturing,
Inc for chimney purchase information.
• Installation of compl
ete chimney flue is required.
• Adhere by local building codes and t
he National Fire Protection Association Rules Nos 31, 54 and 211.
•
It is required to use Selkirk Chimney Systems; brand type is UT (Ultra Temp or Galva Temp).
•
Selkirk Chimney Systems is a double insulated, stainless steel, Class A Chimney Systems that meets the requirements of UL103
and ULC-S629 and complies with the Chapter 11 of NFPA 211, Standard for chimneys, Fireplaces, Vents and Solid Fuel Burning
Appliances.
•
Chimney termination caps are required; installation of spark arresters may be needed in high fire risk areas.
•
Selkirk chimney comes in carious lengths, spanning from eighteen (18) inches to forty-eight (48) inches. Install each section of
piping by placing male and female sections together then twisting them to lock sections together. When installing your chimney
piping, it is recommenced by many chimney suppliers to brace every eight feet. The chimney manufacture also recommends that
the height of the piping does not exceed a total of forty 40 ft.
•
When installing chimney please refer to manufactures recommendations and requirements for adequate clearances.
•
Furnaces come standard with the Selkirk brand, 6”, 8”, or 10” Anchor plate as well as
a 12
” chimney length.
•
Additional chimney components and lengths are available from your local dealer or can be purchased direct from Greentech
Manufacturing Inc. (Toll Free 866-361-7355)
•
Do not attempt to fabricate your own adapters.
•
Do not mix Selkirk Chimney with other manufactured brands.
•
Do not use existing chimney that already connects to other appliances.
•
A major cause of chimney-related fires is failure to maintain required clearances (air spaces) to combustible material. It is of the
utmost importance that the chimney be installed only in accordance with the manufactures stated instructions. These
instructions must be reviewed prior to installation of venting components.
•
Inspections of chimney need to be performed at least annual to ensure of any obstructions due to creosote buildup. When
necessary perform cleaning of chimney to prevent chimney fires.
CHIMNEY - REQUIREMENTS
WARNING!!!
This unit cannot be hooked to a chimney already serving another appliance.
CAUTION!!!
Hot Surfaces: Keep children away. Do not touch during operation.
WARNING!!!
Risk of Fire: Do not operate with fuel loading and / or ash removal doors open. Do not store fuel or
other combustible materials within marked installation clearances. Inspect and clean flues and chimney regularly.
13
Summary of Contents for Crown Royal Stoves Multi-Pass 7200MP
Page 2: ......
Page 4: ......
Page 6: ...6 ...
Page 8: ...8 ...
Page 11: ...FURNACE FLOOR PLAN Model 7200MP Model 7300MP 11 ...
Page 12: ...FURNACE FLOOR PLAN Model 7400MP Model 7500MP 12 ...
Page 22: ...22 ...
Page 30: ...30 ...
Page 31: ...ELECTRICAL WIRING DIAGRAM 7200MP 7300MP 7400MP 31 ...
Page 32: ...ELECTRICAL WIRING DIAGRAM 7500MP 32 ...
Page 38: ...38 ...
Page 42: ...Model 7500MP 42 ...
Page 51: ...51 ...
Page 52: ...OWNER S MANUAL ...