VOLTAGE RATINGS
If the Operator is Working
18 Vac Transformer __________________________ 18.0 to 22.0 Vac
5 W Solar panel (single) _______________________ 18.0 to 22.0 Vdc 300 mA
measure voltage at panel and control box.
12 V Battery ________________________________ 12.0 to 13.5 Vdc 7.0 Ah
Charging circuit _____________________________ 12.0 to 14.8 Vdc
measure voltage with battery connected
PROFESSIONAL ACCESS SYSTEMS
®
The Gate CLOSES Then Opens Again on its Own:
1. Check the position of the mounting brackets and readjust if necessary.
2. Check the gate for binding or hinge damage.
The Gate OPENS Then Closes Again on its Own:
1. Check the position of the mounting brackets and readjust if necessary.
2. Check the gate for binding or hinge damage.