Important Safety Instructions
IMPORTANT SAFETY INSTRUCTIONS Specific to Secondary
Means of Protection Against Entrapment
As specified by Underwriters Laboratories Inc. UL 325 (30A.1.1), automatic gate operators shall have provisions for,
or be supplied with, at least one independent primary and one independent secondary means to protect against
entrapment. GTO gate operators utilize Type A, an inherent entrapment sensing system, as the primary type of
entrapment protection. The GTO/PRO SW-5000 and GTO/PRO SW-6000 operators have provisions for the
connection of Type B1, B2, or D protection to be used as the secondary type of entrapment protection.
1. For gate operators utilizing a non-contact sensor (Type B1) in accordance with UL 325 (51.8.4 [h]):
A. Refer to the sensor manufacturer’s instructions on the placement of non-contact sensors for each type of
application.
B. Care shall be exercised to reduce the risk of nuisance tripping, such as when a vehicle trips the sensor while
the gate is still moving.
C. One or more non-contact sensors shall be located where the risk of entrapment or obstruction exists, such as
the perimeter reachable by a moving gate or barrier.
2. For gate operators utilizing a contact sensor (Type B2) in accordance with UL 325 (51.8.4 [i]):
A. One or more contact sensors shall be located at the leading edge, bottom edge, and post mounted both inside
and outside of a vehicular swing gate system.
B. A hard wired contact sensor shall be located and its wiring arranged so that the communication between the
sensor and the gate operator is not subjected to mechanical damage.
C. A wireless contact sensor such as one that transmits radio frequency (RF) signals to the gate operator for
entrapment protection functions shall be located where the transmission of the signals are not obstructed or
impeded by building structures, natural landscaping or similar obstruction. A wireless contact sensor shall
function under the intended end-use conditions.
3. For gate operators utilizing an actuating device requiring continuous pressure to maintain opening or closing motion
of the gate (Type D) in accordance with UL 325 (51.8.4 [e]):
A. The gate operator controls must be placed so that the user has full view of the gate area when the gate is moving.
B. Warning signs (see page 6) shall be placed adjacent to the controls.
C. An automatic closing device (timer, loop sensor, etc.) shall not be employed.
D. No other activation device shall be connected.
ENTRAPMENT ALARM (UL 325; 30A.1.1A)
The GTO/PRO SW-5000 and GTO/PRO SW-6000 operators are designed to stop and reverse for 2 seconds
when the gate comes in contact with an obstruction or when an object activates the non-contact sensors.
Additionally, these operators are equipped with an audio entrapment alarm which will function if the unit
obstructs twice while opening or closing. This alarm will sound for a period of 5 minutes or until the operator
receives an intended signal (e.g., transmitter signal) and the gate returns to a fully open or fully closed position.