Actions during configuration, device start or plugging in the sensor (for given example):
actual temperature
during configuration
actions
70 °C
Port A1 Off (above max) + Port A2 On (above min)
45 °C
Port A1 On (below max) + Port A2 On (above min)
20 °C
Port A1 On (below max) + Port A2 Off (below min)
Action matrix during operation when limit values are exceeded (for given example):
to "above max" to "below max" to "above min" to "below min"
from "above max"
-
A1 On
A1 On
A1 On + A2 Off
from "below max"
A1 Off
-
-
A2 Off
from "above min"
A1 Off
-
-
A2 Off
from "below min"
A1 Off + A2 On
A2 On
A2 On
-
Only the switching operations for which actions have been defined, are triggered. If
no "On" or "Off" action is defined for a port, the port can never reach this state by ex-
ceeding sensor values. Unless it is the initial state.