Expert Power Control 8001
© 2022 GUDE Systems GmbH
Specifications
Object ID
1 Byte
0x00
Object Length
1 Byte
n1
Object Value
n1 Bytes
"Company Id"
Object ID
1 Byte
0x00
Object Length
1 Byte
n2
Object Value
n2 Bytes
"Product Id"
Object ID
1 Byte
0x00
Object Length
1 Byte
n3
Object Value
n3 Bytes
"Product Version"
4.9.1
Sensor Tables
Important
: All calculations in this chapter are based on addresses starting at "0".
With some Modbus TCP utilities the addresses start at 1. In this case a 1 must be ad-
ded to the addresses in this chapter. Please try both possibilities for tests!
External sensors addresses (Input Register)
Sensor field
Port 1
Temperature
0x100
Humidity
0x101
Digital input
0x102
Air Pressure
0x103
Dew Point
0x104
Dew Point Difference
0x105
A value of 0x8000 means that no sensor is plugged into the corresponding port or the
corresponding field in the sensor is not available.
Line-In Energy Addresses (Input Register)
Offset
Sensor Field
Line 1
0
Absolute Active Energy
0x400
1
Power Active
0x402
2
Voltage
0x404
3
Current
0x406
4
Frequency
0x408
5
Power Factor
0x40a
6
Power Angle
0x40c
7
Power Apparent
0x40e
8
Power Reactive
0x410
9
Absolute Active Energy Resettable
0x412
10
Absolute Reactive Energy
0x414
11
Absolute Reactive Energy Resettable
0x416
12
Reset Time - sec. since Reset
0x418
13
Forward Active Energy
0x41a
14
Forward Reactive Energy
0x41c
15
Forward Active Energy Resettable
0x41e
16
Forward Reactive Energy Resettable
0x420
17
Reverse Active Energy
0x422
Summary of Contents for Expert Power Control 8001