98
Expert Power Control 8221/8226
© 2022 GUDE Systems GmbH
Specifications
Device Resource
Start
End
Modbus Data Type
Power/Output/eFuse Ports
0x000
0x3ff
Coils
DC Inputs
0x400
0x7ff
Discrete Inputs
Stop Condition active
0x800
0x800
Discrete Inputs
POE active
0x801
0x801
Discrete Inputs
Status Power Sources
0x1000
0x100f
Discrete Inputs
OVP active (Line-Ins)
0x1010
0x101f
Discrete Inputs
eFuse Errors
0x1100
0x11ff
Discrete Inputs
Info Area
0x000
0x005
Input Registers
CPU Sensor values
0x080
0x083
Input Registers
External Sensors
0x100
0x1ff
Input Registers
Fan Level
0x200
0x20f
Input Registers
Line Energy Sensors
0x400
0x39ff
Input Registers
Port Energy Sensors
0x3a00
0x81ff
Input Registers
Bank Energy Sensors
0x8200
0x823f
Input Registers
Power Source Sensors
0x8240
0x827f
Input Registers
Residual Current Monitor
0x8280
0x82cf
Input Registers
Bank Power Source Select
0x000
0x00f
Holding Registers
Fan Mode
0x010
0x01f
Holding Registers
This chapter is general for all Gude devices. Depending on the device type, some
ports or certain sensors are not available.
The Unit-ID is ignored because the device is uniquely identified by its IP address.
Supported Modbus TCP Functions
Function
Request Code
Read Coils
0x01
Read Discrete Inputs
0x02
Write Single Coil
0x05
Write Multiple Coils
0x0f
Read Input Registers
0x04
Read Holding Registers
0x03
Write Holding Register
0x06
Write Multiple Holding Registers
0x10
Read Device Identification
0x2B / 0x0E
Coils
Device Resource
Start
End
Device Function
Power/Output/eFuse
0x000
0x3ff
Coil represens Port State
Discrete Inputs
Device Resource
Start
End
Function when set