79
Expert Power Control 8316
© 2022 GUDE Systems GmbH
Specifications
"
system {SWITCH_PORT=0} events type show
show s w hat event types are enabled
system {SWITCH_PORT=0} events mqtt retain set
{OFF=0|ON=1}
sets mqtt retain
system {SWITCH_PORT=0} events mqtt retain
show
show s if mqtt retain set
system panel enabled set {OFF=0|ON=1}
blocks panel buttons w hen not enabled
system panel enabled show
show s if panel buttons are enabled
system panel port all set {OFF=0|ON=1}
enable siw tch all relays from panel buttons
system panel port all show
show s if siw tch all relays from panel buttons
enabled
system sensor {VSYS=0|VAUX=1|VMAIN=2|
TCPU=3} show
show s internal sensors if model supports it
timer
enters cmd group "timer"
timer enabled set {OFF=0|ON=1}
enables timer functions
timer enabled show
show s if timer a enabled
timer syslog facility set {0..23}
sets facility level for timer syslog
timer syslog facility show
show s facility level for timer syslog
timer syslog verbose set {0..7}
sets verbose level for timer syslog
timer syslog verbose show
show s verbose level for timer syslog
timer {rule_num} enabled set {OFF=0|ON=1}
enables rule
timer {rule_num} enabled show
show s if rule is enabled
timer {rule_num} name set "{name}"
sets name of rule
timer {rule_num} name show
show s name of rule
timer {rule_num} {FROM=0|UNTIL=1} set "{yyyy-
mm-dd}"
sets date range of rule
timer {rule_num} {FROM=0|UNTIL=1} show
show s date range of rule
timer {rule_num} trigger jitter set {0..65535}
sets jitter for rule
timer {rule_num} trigger jitter show
show jitter of rule
timer {rule_num} trigger random set {0..100}
sets probability for rule
timer {rule_num} trigger random show
show s rule probability
timer {rule_num} trigger {HOUR=0|MIN=1|SEC=2|
DAY=3|MON=4|DOW=5} set "{time_date_list}"
sets time date list
timer {rule_num} trigger {HOUR=0|MIN=1|SEC=2|
DAY=3|MON=4|DOW=5} show
show s time date list
timer {rule_num} action mode set {SWITCH=1|
CLI=2}
sets sw itch or cli cmd
timer {rule_num} action mode show
show s if sw itch or cli cmd
timer {rule_num} action {SWITCH1=0|SWITCH2=1}
{OFF=0|ON=1} set "{port_list}"
sets port list for sw itch cmd
timer {rule_num} action {SWITCH1=0|SWITCH2=1}
{OFF=0|ON=1} show
show s port list for sw itch cmd
timer {rule_num} action delay set {0..65535}
delay betw een cmds
timer {rule_num} action delay show
show s delay betw een cmds
timer {rule_num} action console set "{cmd}"
sets cmd string
timer {rule_num} action console show
show s cmd string
timer {rule_num} action hash set "{data}"
sets action binary form
timer {rule_num} action hash show
show s action binary form
timer {rule_num} delete
delete one timer
timer delete all
delete all timer
vt100
enters cmd group "vt100"
vt100 echo set {OFF=0|ON=1}
sets console echo state
vt100 echo show
show s console echo state
vt100 numeric set {OFF=0|ON=1}
sets numeric mode
vt100 numeric show
show s numeric mode state
vt100 reset
resets terminal
Notes
1. Legacy - The command has been replaced by a newer version
2. Command can be entered on any level
Summary of Contents for Expert Power Control 8314
Page 2: ...2 Expert Power Control 8316 2022 GUDESystems GmbH ...
Page 5: ...Device Description ...
Page 12: ...Operating ...
Page 23: ...Configuration ...
Page 51: ...Specifications ...
Page 104: ...104 Expert Power Control 8316 2022 GUDESystems GmbH Specifications ...
Page 105: ...Support ...