75
Expert PDU Energy 8311
© 2022 GUDE Systems GmbH
Specifications
Device Identification
Returns manufacturer name and device identification:
Request Code
1 Byte
0x2b
MEI Type
1 Byte
0x0e
Read Dev ID code
1 Byte
0x01
Object Id
1 Byte
0x00
Response Code
1 Byte
0x2b
MEI Type
1 Byte
0x0e
Read Dev ID code
1 Byte
0x01
Conformity Level
1 Byte
0x01
More Follows
1 Byte
0x00
NextObjectID
1 Byte
0x00
Number of Objects
1 Byte
0x03
Object ID
1 Byte
0x00
Object Length
1 Byte
n1
Object Value
n1 Bytes
"Company Id"
Object ID
1 Byte
0x00
Object Length
1 Byte
n2
Object Value
n2 Bytes
"Product Id"
Object ID
1 Byte
0x00
Object Length
1 Byte
n3
Object Value
n3 Bytes
"Product Version"
4.9.1
Sensor Tables
Important
: All calculations in this chapter are based on addresses starting at "0".
With some Modbus TCP utilities the addresses start at 1. In this case a 1 must be ad-
ded to the addresses in this chapter. Please try both possibilities for tests!
External sensors addresses (Input Register)
Sensor field
Port 1
Temperature
0x100
Humidity
0x101
Digital input
0x102
Air Pressure
0x103
Dew Point
0x104
Dew Point Difference
0x105
A value of 0x8000 means that no sensor is plugged into the corresponding port or the
corresponding field in the sensor is not available.
Line-In Energy Addresses (Input Register)
Offset
Sensor Field
Line 1
Summary of Contents for 8311-1
Page 2: ...2 Expert PDU Energy 8311 2022 GUDESystems GmbH...
Page 5: ...Device Description...
Page 11: ...11 Expert PDU Energy 8311 2022 GUDESystems GmbH Device Description...
Page 12: ...Operating...
Page 22: ...Configuration...
Page 45: ...Specifications...
Page 80: ...Support...
Page 85: ...85 Expert PDU Energy 8311 2022 GUDESystems GmbH Index Timer 35 Timer Configuration 35 TLS 54...