9
Expert PDU energy 8310
Configuration
Enable IP Filter
4.3.2.2
Here you can activate the IP Access Control List (IP ACL).
If IP ACL is active, DHCP and SNMP only work, if all necessary servers and clients are registered in this list.
Configuration - HTTP
4.3.3
HTTP Port
4.3.3.1
Here you can enter the HTTP port number, if necessary. Possible numbers are 1 ... 65534 (standard: 80). To get access, you
have to enter the port number after the IP address of the device
,
e.g.:
http://192.168.0.2:1720
For the changes to get valid a restart of the firmware is required.
Require HTTP Password
4.3.3.2
Password protected access can be activated here. In this case, a user and an admin password have to be defined. Pass-
words have a maximum lengths of 15 characters.
Administrators are authorized to modify the settings. The username of the admin is
“admin”
.
Users are authorized to login, but are not allowed to modify the settings. The username of the user is
“user”
.
If you have forgotten your password, activate the bootloader mode, start GBL-Conf.exe and deactivate the password request.
For the changes to get valid a restart of the firmware is required.
Check Password on start page
4.3.3.3
If activated, the user has to enter his password, before logging in to the webinterface.