5
Expert PDU energy 8310
Hardware
Usage and Display
3.3
Status LED
The status LED shows directly the state of the device:
Red: The device is not connected to the Ethernet.
Orange: The device is connected to the Ethernet, TCP/IP settings are not defined.
Green: Your device is connected to the Ethernet, TCP/IP settings are assigned.
regularly flashing: The device is in bootloader mode.
Display views
Durch Drücken des "
select
" Tasters können verschiedene Informationen und Messwerte auf dem Display abgerufen werden.
Bei jedem Druck auf den Taster wird eine neue Seite auf dem LCD Display angezeigt:
By pressing the "
select
" button various informations and statistics are available on the display. Each time you press the but-
ton a new page is shown on the LCD display:
227V
0.0A 0W
0.000kWh
This is the usual energy view. On the top line is printed voltage, current and power. The bottom line shows the consumed
energy (unit kWh). After 10 seconds of waiting time every other page will resume to this view.
7:48:59 h:m:s
0.000kWh
This page shows in the bottom line the power meter and on the top line the period of time over the power was measured. The
values ??are stored in an EEPROM every 5 minutes and therefore preserved during a power outage.
VRMS
225.3V
IRMS
0.000A
Here, voltage and current are shown.
Active
0W
Reactive
0VAR
Active power and reactive power are shown.
Apparent
0VA
Phase
-83.5deg
The measured values ??of apparent power and the phase angle of the power.