10
Expert Power Control 8221/8226
© 2021 GUDE Systems GmbH
Device Description
1 x Serial connector (D-SUB, RS232)
2 x Mains supply (IEC C20, max.16 A)
2 x 6 Load outputs (IEC C13, max. 16
A)
2 x RJ45 for external sensor
Network connectivity
10/100 MBit/s 10baseT Ethernet
Protocols
TCP/IP, HTTP/HTTPS, SNMP
v1/v2c/v3,
SNMP traps, Syslog, E-Mail (SMTP)
Power Supply
internal power supply (90-265V AC / -
15% / +10%)
Overvoltage Protection
·
single peak current for 20/80us pulse
·
max. clamping voltage 20/80us pulse,
Ipk = 100 A
20 mm / 250 J varistor disk (300V AC)
10000 A
775 V
Environment
·
Operating temperature
·
Storage temperature
·
Humidity
0°C - 50 °C
-20°C - 70 °C
0% - 95% (non-condensing)
Case
powder coated, galvanized steel sheet
Measurements
19" (inches), 1 Rack Unit, (Depth 195
mm)
Weight
approx. 2.9 kg (8221-1)
approx. 3.0 kg (8226-1)
1.7.1
Electrical Measurement
typical fault tolerances for Ta=25°C, I=1Arms...16Arms, Un=90Vrms...265Vrms
Electrical Measurement Specification
Category
Range
Unit
Resolu-
tion
Inaccuracy
(typical)
Voltage
90-265
V
0.01
< 1%
Current
0 - 16
A
0.001
< 1.5%
Frequency
45-65
Hz
0.01
< 0.03%
Phase
-180 - +180
°
0.1
< 1%
Active power
0 - 4000
W
1
< 1.5%
Reactive power 0 - 4000
Var
1
< 1.5%
Apparent power 0 - 4000
VA
1
< 1.5%
Power factor
0 - 1
-
0.01
< 3%
Energy Counter
Active Energy
(total)
9.999.999,999
kWh
0.001
< 1.5%
Active Energy
(temporary)
9.999.999,999
kWh
0.001
< 1.5%
Summary of Contents for Expert Power Control 8221 Series
Page 2: ...2 Expert Power Control 8221 8226 2021 GUDE Systems GmbH ...
Page 5: ...Device Description ...
Page 13: ...13 Expert Power Control 8221 8226 2021 GUDE Systems GmbH Device Description ...
Page 14: ...Operating ...
Page 24: ...Configuration ...
Page 50: ...Specifications ...
Page 91: ...Support ...