23
8. Readings on LCD display
°C, °F
reading next to this symbol is measured temperature or error state of value
%RH
reading next to this symbol is measured relative humidity or error state of value
hPa, PSI, inHg
reading next to this symbol is measured pressure or error state of value. If selected
pressure unit is
mBar
or
oz/in
2
or
mmHg
or
inH
2
O
or
kPa
, there is shown only value
(number) without corresponding pressure unit!
°C / °F DP
reading next to this symbol is calculated dew point temperature or error state of value
g/m
3
reading next to this symbol is calculated absolute humidity or error state of value
g/kg
reading next to this symbol is calculated specific humidity or mixing ratio (depends on device
setting) or error state of value
3
this symbol is on if jumper is closed
If specific enthalpy is selected, there is shown only value (number) without corresponding unit.
9. Preventive maintenance and calibration
Pay heed to recommended calibration interval. Do not subject the device to mechanical stress.
10. Technical specification
10.1. Technical parameters
10.1.1. Common parameters
Power voltage:
9 to 30 V DC
Power consumption:
approx. 1 W + consumption of sensors and detectors connected to
+U terminals
Measuring interval:
temperature, relative humidity . . . . . 0,5s
barometric pressure . . . . . . . . . . . . . 2s
Display switching interval
: 4 s (when more than two values are displayed)
Relay outputs:
Amount:
2
Maximal voltage:
50 V
Maximal current:
2A
Maximal power:
60 VA
Relays contact is not designed for direct control of line voltage!
(output relay contact parameters: max 220Vdc, 125Vac, 2A, 60 W, 62.5 VA)
Binary inputs:
Amount: 3
Signal for binary input: from floating contact or binary voltage
Caution! Binary inputs are NOT galvanic isolated!
Minimal input pulse duration: 500 ms (detection of shorter pulses is not guaranteed)
Current through closed contact: 25
A
Open contact voltage: < 3,3 V
Maximal input voltage: +30 V