GGW / AGW Glycol protector - Assembly instructions
Choose one of three actuator positions on
valve body. Positioning of actuator deter-
mines position of pan. When installing the
valve observe direction of flow indicated
by arrow on valve. Screw valve onto wel-
ded cone at drainage point of GGW Glycol
protector.
To allow condensation to be drained, a
second ¾
"
connection can be used. Make
sure to provide a bleeding function, the-
reby eliminating the risk of the separator
running dry. Electrical connections to be
made according to connection plan.
A cover is provided for every valve. Make
sure to install it when running the device in
an outside area.
We can supply you with a copper adapter
which includes a Schrader-Valve to be sol
-
dered into place. Please take note to re-
move the Schrader-Valve during soldering.
Screw pressure sensor onto existing or
newly attached test port. Pressure sen-
sor to be tightened with max 30 NM to
avoid damage. When connecting the pres-
sure sensor, refer to connection dia-
gramm (Page 14). A 5 m cable is included
with the pressure sensor for ½
"
external
thread-connection. Position the two wires
according to connection plan.
Safety valve with actuator