15
GGW / AGW Glycol protector - Assembly instructions
Recommendations for cable routing::
•
Supply cable for switch box: NXM 3x1.5²
• Control cable for pressure sensor switch box: Olflex 2x0.75² (shielded)
• Supply cable for valve switch box: Olflex 2x1.5²
• Control cable for valve switch box: Olflex 4x1.5²
UV-resistant if exposed to sun light
Connection Voltage supply switch box (1.5 mm²)
•
Ph, terminal L 1
•
N, blue terminal strip
•
Ph, green terminal strip
•
Connect pressure sensor, (0.8 mm²)
•
Terminal block switch box, terminal block pressure sensor
•
Terminal 7 = terminal 1 (white)
•
Terminal 8 = terminal 2 (brown)
Connecting valves (1.5 mm²)
Terminal block switch box, terminal block valves
•
Terminal 17 = terminal 1 (brown)
•
Terminal 23 = terminal 2 (blue)
•
Terminal 11 = terminal S4 (4)
•
Terminal 12 = terminal S5 (5)
•
Terminal 13 = terminal S1 (1)
•
Terminal 14 = terminal S3 (3)
Note:
Make sure the display is clearly visible when mounting the control
module.
For any questions regarding assembly, implementation or service
please contact our
service telephone
at: +49
5921 71347 - 0
.
Connection plan