General Description:

 The Switch/Proximity Detector Repeater type D1130 is a DIN Rail unit with one or two independent channels. The unit can be configured for contact or proximity 

detector, NO or NC and for NE or ND SPDT relay output contact. Each channel enables a Safe Area load to be controlled by a switch, or a proximity detector, located in Hazardous Area. 

D1130D dual channel 

type has two independent input channels and actuates the corresponding output relay. Two actuation modes can be independently DIP switch configured on 

each input channel: NO input/NE relay or NO input/ND relay. Contact or proximity sensor and its connection line short or open circuit fault detection is also DIP switch configurable: 

fault detection can be enabled (in case of fault it de-energizes the corresponding output relay and turns the fault LED on) or disabled (in case of fault the corresponding output relay 

repeats the input line open or closed status as configured). 

D1130S single channel 

type has one input channel and two output relays; the unit has two DIP switch configurable operating modes: 

Mode A) input channel actuates in parallel the two output relays (DPDT contact). Relay actuation mode can be independently configured for each output in two modes: NO input/NE 

relay or NO input/ND relay. 

Mode B) input channel actuates output relay A configurable in two modes as in mode A above. Output relay B operates as a fault output (in case of input fault, relay B actuates and the 

fault LED turns on while relay A repeats the input line as configured). 

Actuation can be DIP switch configured in two modes: No input fault/energized relay (it de-energizes in case of fault) or No input fault/de-energized relay (it energizes in case of fault). 

Function:

 1 or 2 channels I.S. switch repeater for contact or EN60947-5-6 proximity. Provides 3 port isolation (input/output/supply). 

Signalling LEDs:

 Power supply indication (green), output status (yellow), line fault (red). 

Field Configurability:

 NO/NC input for contact/proximitor, NE/ND relay operation and fault detection enable/disable. 

EMC: 

Fully compliant with CE marking applicable requirements. 

Supply: 

115-230 Vac, 50-60 Hz nom (85 to 250 Vac, 48 to 400 Hz), ripple within voltage limits 

 10 Vpp. Limit supply voltage to 250 Vrms for Instrinsic Safety applications. 

Current consumption @ 115 Vac: 

25 mA with short input and relays energized. 

Current consumption @ 230 Vac: 

15 mA with short input and relays energized. 

Max. power consumption: 

at 250 Vac supply voltage, short circuit input and relays energized, 2.0 W for 2 channels D1130D, 1.9 W for 1 channel D1130S. 

Isolation (Test Voltage):

 I.S. In/Out 2.5 KV; I.S. In/Supply 2.5 KV; Out/Supply 2.5 KV; Out/Out 2.5 KV. 

Input switching current levels:

 ON 

 2.1 mA, OFF 

 1.2 mA, switch current 

 1.65 mA ± 0.2 mA hysteresis. 

Fault current levels: 

open fault 

 0.2 mA, short fault 

 6.8 mA 

(when enabled both faults de-energize channel relay with dual channel unit D1130D or actuate fault relay with single channel unit D1130S). 

Input equivalent source: 

8 V 1 K

 typical (8 V no load, 8 mA short circuit). 

Output: 

voltage free SPDT relay contact. 

Contact material: 

AgCdO. 

Contact rating: 

2 A 250 Vac 500 VA, 2 A 250 Vdc 80 W (resistive load). 

DC Load breaking capacity: 

Mechanical / Electrical life: 

30 * 10

6

 / 1 * 10

5

 operation, typical. 

Operate / Release time: 

7 / 3 ms typical. 

Bounce time NO / NC contact: 

3 / 5 ms. 

Response time: 

20 ms. 

Frequency response: 

10 Hz maximum. 

Compatibility: 

 

CE mark compliant, conforms to 94/9/EC Atex Directive and to 2004/108/CE EMC Directive. 

Environmental conditions: 

Operating: 

temperature limits -20 to + 60 °C, relative humidity max 90 % non condensing, up to 35 °C. 

Storage: 

temperature limits – 45 to + 80 °C. 

Safety Description: 

II (1) G [Ex ia Ga] IIC, II (1) D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I, II 3G Ex nA IIC T4, [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I associated electrical apparatus. 
Uo/Voc = 10.7 V, Io/Isc = 15 mA, Po/Po = 39 mW at terminals 13-14, 15-16. 
Um = 250 Vrms, -20 °C 

 Ta 

 60 °C. 

Approvals: 

DMT 01 ATEX E 042 X conforms to EN60079-0, EN60079-11, EN60079-26, EN61241-0, EN61241-11, 

IECEx BVS 07.0027X conforms to IEC60079-0, IEC60079-11, IEC60079-26, IEC61241-0, IEC61241-11, GM International CRR028 conforms to EN60079-0, EN60079-15, 
UL & C-UL E222308 conforms to UL913 (Div.1),UL 60079-0 (General, All Zones), UL60079-11 (Intrinsic Safety “i” Zones 0 & 1) for UL and 
CSA-C22.2 No.157-92 (Div.1), CSA-E60079-0 (General, All Zones), CSA-E60079-11 (Intrinsic Safety “i” Zones 0 & 1) for C-UL, 
refer to control drawing ISM0143 for complete UL and C-UL safety and installation instructions, 
FM & FM-C No. 3024643, 3029921C, conforms to Class 3600, 3610, 3611, 3810 and C22.2 No.142, C22.2 No.157, C22.2 No.213, E60079-0, E60079-11, E60079-15, 
Russia according to GOST 12.2.007.0-75, R 51330.0-99, R 51330.10-99 [Exia] IIC X, Ukraine according to GOST 12.2.007.0,22782.0,22782.5 Exia IIC X, 
DNV and KR Type Approval Certificate for marine applications. 

Mounting: 

T35 DIN Rail according to EN50022. 

Weight:

 

about 145 g D1130D, 140 g D1130S. 

Connection:

 by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm

2

Location:

 Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA 

T4 installation. 

Protection class:

 IP 20. 

Dimensions:

 Width 22.5 mm, Depth 99 mm, Height 114.5 mm. 

 

 

 

Technical Data 

Characteristics 

0.2

0.1

V (V)

I (A)

10

20

30

40

50

100

200

300

0.3 0.5

1

2

5

Resistive 

Load

Summary of Contents for D1130D

Page 1: ...D1130 Switch Proximity Detector Repeater Relay Output ISM0048 8 D1130S D1130D INSTRUCTION MANUAL INSTRUCTION MANUAL Switch Proximity Detector Repeater Relay Output DIN Rail Models D1130S D1130D ...

Page 2: ...channels D1130D 1 9 W for 1 channel D1130S Isolation Test Voltage I S In Out 2 5 KV I S In Supply 2 5 KV Out Supply 2 5 KV Out Out 2 5 KV Input switching current levels ON 2 1 mA OFF 1 2 mA switch current 1 65 mA 0 2 mA hysteresis Fault current levels open fault 0 2 mA short fault 6 8 mA when enabled both faults de energize channel relay with dual channel unit D1130D or actuate fault relay with si...

Page 3: ...ut for fault detection on single channel version Three port isolation Input Output Supply EMC Compatibility to EN61000 6 2 EN61000 6 4 In field programmability by DIP Switch ATEX IECEx UL C UL FM FM C Russian and Ukrainian Certifications Type Approval Certificate DNV and KR for marine applications High Reliability SMD components High Density two channels per unit Simplified installation using stan...

Page 4: ... Normally Opened NO 2 L Power Supply 115 230 Vac 3 N Power Supply 115 230 Vac 4 Output Ch 2 Common 5 Output Ch 2 Relay Normally Opened NO 6 Output Ch 2 Relay Normally Closed NC 7 Output Ch 1 Relay Normally Closed NC 8 D1130S Input Ch 1 for Proximity or Input Ch 1 for Voltage free Contact HAZARDOUS AREA SAFE AREA Input Ch 1 for Proximity or Input Ch 1 for Voltage free Contact 13 14 Output Ch 1 A Co...

Page 5: ...pparatus Parameters Ci Ci device C cable Li Li device L cable Li Ri device and L cable R cable IIC A B Co Ca 2 23 µF Co Ca 15 6 µF Co Ca 69 µF IIB C IIA D IIC A B Lo La 172 mH Lo La 689 mH Lo La 1379 mH IIB C IIA D IIC A B Lo Ro 930 µH Ω Lo Ro 3720 µH Ω Lo Ro 7440 µH Ω IIB C IIA D NOTE for USA and Canada IIC equal to Gas Groups A B C D E F and G IIB equal to Gas Groups C D E F and G IIA equal to G...

Page 6: ...NE 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1130D 13 14 3 L 4 N 8 NC 2 NO 1 COM Supply 115 230 Vac Out 1 In 1 15 16 7 NC 6 NO 5 COM In 2 Out 2 voltage free Contact Proximity Proximity Common positive connection _ voltage free Contact MODEL D1130S 13 14 8 NC 2 NO 1 COM Out 1 A In 1 7 NC 6 NO 5 COM Out 1 B voltage free Cont...

Page 7: ...ult condition of sensor and connecting line are displayed by signaling LEDs green for power yellow for status and red for fault condition D1130D dual channel type has two independent input channels and actuates the corresponding output relay SPDT contact two actuation modes can be independently DIP switch configured for each input channel Normally open input Normally energized relay or Normally cl...

Page 8: ...50022 D1130 unit can be mounted with any orientation over the entire ambient temperature range see section Installation in Cabinet and Installation of Electronic Equipments in Cabinet Instruction Manual D1000 series for detailed instructions Electrical connection of conductors up to 2 5 mm are accommodated by polarized plug in removable screw terminal blocks which can be plugged in out into a powe...

Page 9: ...tection ON IN OUT Operation NO NE or NC ND NO ND or NC NE ON 1 OFF 4 4 3 3 Disabled contact proximity sensor Enabled proximity sensor or contact with terminating line resistor ON 13 2 OFF NO 14 1 2 8 NE OR NC 13 14 1 2 8 ND 13 NO 14 1 2 8 NE OR NC 13 14 1 2 8 ND Side A Panel View Input Output Input Output Output Input Output Input CH2 Setting Line fault detection ON IN OUT Operation NO NE or NC ND...

Page 10: ...led proximity sensor or contact with terminating line resistor Out B Out A 1 2 8 5 6 7 Out A 1 2 8 Out B 5 6 7 No Fault 5 6 7 5 6 7 NE NE NE ND ND NE No Fault D1130D Configuration Summary Table Channel IN OUT Operation NO NE or NC ND NO ND or NC NE SW2 OFF SW4 OFF ON 1 2 Channel Line fault detection Disabled contact proximity sensor Enabled proximity sensor or contact with terminating line resisto...