background image

 

D1130 

- Switch / Proximity Detector Repeater Relay Output 

G.M. International ISM0048-8 

D1130D 

+ Input Ch 1 for Proximity or 
Input Ch 1 for Voltage free Contact 

Terminal block connections 

HAZARDOUS AREA 

SAFE AREA 

- Input Ch 1 for Proximity or 
Input Ch 1 for Voltage free Contact 

+ Input Ch 2 for Proximity or 
Input Ch 2 for Voltage free Contact 

- Input Ch 2 for Proximity or 
Input Ch 2 for Voltage free Contact 

13

 

14

 

15

 

16

 

Output Ch 1 Common 

1

 

Output Ch 1 Relay Normally Opened (NO) 

2

 

L Power Supply 115-230 Vac 

3

 

N Power Supply 115-230 Vac 

4

 

Output Ch 2 Common 

5

 

Output Ch 2 Relay Normally Opened (NO) 

6

 

Output Ch 2 Relay Normally Closed (NC) 

7

 

Output Ch 1 Relay Normally Closed (NC) 

8

 

D1130S 

+ Input Ch 1 for Proximity or 
Input Ch 1 for Voltage free Contact 

HAZARDOUS AREA 

SAFE AREA 

- Input Ch 1 for Proximity or 
Input Ch 1 for Voltage free Contact 

13

 

14

 

Output Ch 1-A Common 

1

 

Output Ch 1-A Relay Normally Opened (NO) 

2

 

L Power Supply 115-230 Vac 

3

 

N Power Supply 115-230 Vac 

4

 

Output Ch 1-B Common 

5

 

Output Ch 1-B Relay Normally Opened (NO) 

6

 

Output Ch 1-B Relay Normally Closed (NC) 

7

 

Output Ch 1-A Relay Normally Closed (NC) 

8

 

Summary of Contents for D1130D

Page 1: ...D1130 Switch Proximity Detector Repeater Relay Output ISM0048 8 D1130S D1130D INSTRUCTION MANUAL INSTRUCTION MANUAL Switch Proximity Detector Repeater Relay Output DIN Rail Models D1130S D1130D ...

Page 2: ...channels D1130D 1 9 W for 1 channel D1130S Isolation Test Voltage I S In Out 2 5 KV I S In Supply 2 5 KV Out Supply 2 5 KV Out Out 2 5 KV Input switching current levels ON 2 1 mA OFF 1 2 mA switch current 1 65 mA 0 2 mA hysteresis Fault current levels open fault 0 2 mA short fault 6 8 mA when enabled both faults de energize channel relay with dual channel unit D1130D or actuate fault relay with si...

Page 3: ...ut for fault detection on single channel version Three port isolation Input Output Supply EMC Compatibility to EN61000 6 2 EN61000 6 4 In field programmability by DIP Switch ATEX IECEx UL C UL FM FM C Russian and Ukrainian Certifications Type Approval Certificate DNV and KR for marine applications High Reliability SMD components High Density two channels per unit Simplified installation using stan...

Page 4: ... Normally Opened NO 2 L Power Supply 115 230 Vac 3 N Power Supply 115 230 Vac 4 Output Ch 2 Common 5 Output Ch 2 Relay Normally Opened NO 6 Output Ch 2 Relay Normally Closed NC 7 Output Ch 1 Relay Normally Closed NC 8 D1130S Input Ch 1 for Proximity or Input Ch 1 for Voltage free Contact HAZARDOUS AREA SAFE AREA Input Ch 1 for Proximity or Input Ch 1 for Voltage free Contact 13 14 Output Ch 1 A Co...

Page 5: ...pparatus Parameters Ci Ci device C cable Li Li device L cable Li Ri device and L cable R cable IIC A B Co Ca 2 23 µF Co Ca 15 6 µF Co Ca 69 µF IIB C IIA D IIC A B Lo La 172 mH Lo La 689 mH Lo La 1379 mH IIB C IIA D IIC A B Lo Ro 930 µH Ω Lo Ro 3720 µH Ω Lo Ro 7440 µH Ω IIB C IIA D NOTE for USA and Canada IIC equal to Gas Groups A B C D E F and G IIB equal to Gas Groups C D E F and G IIA equal to G...

Page 6: ...NE 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1130D 13 14 3 L 4 N 8 NC 2 NO 1 COM Supply 115 230 Vac Out 1 In 1 15 16 7 NC 6 NO 5 COM In 2 Out 2 voltage free Contact Proximity Proximity Common positive connection _ voltage free Contact MODEL D1130S 13 14 8 NC 2 NO 1 COM Out 1 A In 1 7 NC 6 NO 5 COM Out 1 B voltage free Cont...

Page 7: ...ult condition of sensor and connecting line are displayed by signaling LEDs green for power yellow for status and red for fault condition D1130D dual channel type has two independent input channels and actuates the corresponding output relay SPDT contact two actuation modes can be independently DIP switch configured for each input channel Normally open input Normally energized relay or Normally cl...

Page 8: ...50022 D1130 unit can be mounted with any orientation over the entire ambient temperature range see section Installation in Cabinet and Installation of Electronic Equipments in Cabinet Instruction Manual D1000 series for detailed instructions Electrical connection of conductors up to 2 5 mm are accommodated by polarized plug in removable screw terminal blocks which can be plugged in out into a powe...

Page 9: ...tection ON IN OUT Operation NO NE or NC ND NO ND or NC NE ON 1 OFF 4 4 3 3 Disabled contact proximity sensor Enabled proximity sensor or contact with terminating line resistor ON 13 2 OFF NO 14 1 2 8 NE OR NC 13 14 1 2 8 ND 13 NO 14 1 2 8 NE OR NC 13 14 1 2 8 ND Side A Panel View Input Output Input Output Output Input Output Input CH2 Setting Line fault detection ON IN OUT Operation NO NE or NC ND...

Page 10: ...led proximity sensor or contact with terminating line resistor Out B Out A 1 2 8 5 6 7 Out A 1 2 8 Out B 5 6 7 No Fault 5 6 7 5 6 7 NE NE NE ND ND NE No Fault D1130D Configuration Summary Table Channel IN OUT Operation NO NE or NC ND NO ND or NC NE SW2 OFF SW4 OFF ON 1 2 Channel Line fault detection Disabled contact proximity sensor Enabled proximity sensor or contact with terminating line resisto...