Parameters "Weighting interior / exterior"
Options: 0% / 100%
10% / 90%
...
100% / 0%
This parameter is visible when selecting "Internal and External sensor" in the sensor type, it can set
the proportion between the measured temperature of Thermostat sensor and an external sensor. For
example, the option is "40% / 60%", so, the panel temperature sensor (A) occupies 40%, an external
sensor (B) occupies 60%, temperature control = (the temperature × 40% A) + (the temperature of B ×
60%), Thermostat will control temperature according to the calculated temperature control which send
by the "Actual temperature". This is the proportion summing process.
Parameters "Send temperature at variation of (
℃
)"
Options: Do not send
0.1
0.2
…
3
This parameter define "Actual temperature" can send the current temperature to the bus when a
certain amount of temperature change.
If the option is "Do not send", the temperature only be sent to the bus through the "Actual
temperature", because the temperature measurement value is not automatically transmitted to the bus
If an option is "3", the "Actual temperature" can send the current temperature to the bus when the
temperature reached changes at least 3
℃
,
Parameter "Monitoring time of external sensor in min (0 = inactive)"
Options : 0 ... 255 min
This parameter will be visible when choosing "external sensor" or "internal and external sensor"
about sensor type, to set monitoring time of the thermostat panel to external temperature sensor. If