27
forcing switchover
Window status
Presence object
Operating mode
switchover
Work pattern
to be activated
01
x
x
x
Comfort
02
x
x
x
Standby
03
x
x
x
Night
04
x
x
x
Frost/heating
protection
00
1
x
x
Frost/heating
protection
00
0
1
x
Comfort
00
0
0
01
Comfort
00
0
0
02
Standby
00
0
0
03
Night
00
0
0
04
Frost/heating
protection
Parameter “Send setpoint”
Options
:
do not send
on change
cyclically
on change and cyclically
In the Parameter of “Send setpoint”, the ways of sending the temperature setpoint can be set.
When choosing “do not send”
,
the temperature setpoint won’t be sent. It only can be sent to the bus
after reading by “setpoint temperature”.
When choosing “on change”, the temperature setpoint will be sent to the bus after the changing of
temperature setpoint.
When choosing “cyclically”, the temperature setpoint will be sent to the bus recurrently. Once the
temperature setpoint are changed, it will be sent one week later.
When choosing “on change and cyclically”, the temperature setpoint will be sent to the bus
recurrently. Once the temperature setpoint are changed, it will be sent immediately. Cycling time starts
over.