4.8 Parameter window "Fan Coil Heating/Cooling"
Parameter window "Fan Coil Heating/Cooling”, shown in Figure 4.8
Figure 4.8 Parameter window "Fan Coil Heating/Cooling"
Parameter "Automatic return from manual adjustment"
Options: 1- 255
This parameter sets time of "Automatic return from manual adjustment". After user manually
switching the wind speed, the wind speed reaches the time to return to the automatic mode, the
communication object 21 sends packets to return to automatic speed mode.
Parameter "Threshold value in % for fan speed 1 at heating"
Parameter "Threshold value in % for fan speed 2 at heating"
Parameter "Threshold value in % for fan speed 3 at heating"
Options: 0- 100
"Threshold value in% for fan speed 1 at heating”: to set packet value that "communication
object 22-Fan manual stage" outputs when the Thermostat is switched to high speed 1.
"Threshold value in% for fan speed 2 at heating”: to set packet value that "communication
object 22-Fan manual stage" outputs when the Thermostat is switched to high speed 2