4.9.1 Temperature threshold value
Figure 4.9.1 Parameter window "Temperature threshold value 1/2"
Parameter "Temperature threshold value (×0.1
℃
)"
Options: 0- 500
This parameter sets a high threshold value of temperature, this threshold value can be changed as
"change temperature threshold value1 / 2", and once changing, in the bus will save the new value when
the power of the BUS is off.
Parameter "Negative hysteresis temperature (×0.1
℃
)"
Options: 5- 50
This parameter is used to set the hysteresis value of the low threshold value to high threshold value.
Assuming the hysteresis value is 3
℃
, then the lower threshold = high threshold value -3
℃
. When the
high threshold changes, the low threshold changes accordingly.
Parameter "If temperature is lower than threshold value"
Parameter "If temperature is upper than threshold value"
Options: do not send telegram
send following telegram once
send following telegram cyclically
These two parameters are used to respectively set ways of sending telegram to the object