GVS K-BUS
○
R
KNX/EIB
Thermostat
www.video-star.com.cn
marketing@video-star.com.cn
Tel.
:
(
8620
)
39338986
Fax.
:(
8620
)
39338465
56
Options: AND
OR
XOR
This parameter sets the logic operations results or relations of "Input 3 (6)" and "Input 1 (4)"/"Input 2
(5)", providing three kinds of logic operations relations: “AND", “OR", "XOR".
Parameter "if logic result=‘0/1'"
Options: do not send telegram
send following telegram once
send following telegram cyclically
Here is to set the way of the logic object sends value when the logic results are "1" and "0".
If select "do not send telegram", the object does not sends telegram;
If select "send following telegram once", the object sends telegram once;
If select "send cyclically", the object sends telegram cyclically, sending time can be set in the
following parameter "cycle time for humidity threshold value [min]" in the settings, you can send two
object types, the value of the object is set. in the following parameters "logic1bit / 1byte telegram value "
Parameter "logic 1 bit /1byte telegram value"
Options: 1bit (0~1)
1byte
(
0~255
)
Here is to set the value of the logic object sends when the logic results are "1" and "0".
Parameter "cycle time for logic [min]"
This parameter is used to set the interval of the object "logic 1/2, 1bit/1byte output" cyclically sends
on the bus, only when the parameter "if logic result=0/1" set cyclically sending, is it enabled.
Parameter "use block of the logic 1/2 output"
Options: yes
no
This parameter sets whether to disable the threshold value, if enabled, the object "logic 1/2 block" is
visible, when the object receives telegram "1",
threshold value is disabled, when the object receives