GVS K-BUS
○
R
KNX/EIB
Thermostat
www.video-star.com.cn
marketing@video-star.com.cn
Tel.
:
(
8620
)
39338986
Fax.
:(
8620
)
39338465
79
Bit0: flag of enabling comfort mode 1---enable
0----disable
Bit1: flag of enabling standby mode 1---enable
0----disable
Bit2: flag of enabling night mode 1---enable
0----disable
Bit3: flag of enabling frost / heat protection mode 1---enable
0----disable
Bit4: flag of disable temperature control 1---disable
0----enabled
Bit5: flag of heating/cooling 0—cooling 1—heating.
Bit6: flag of dead zone Select both heating and cooling control functions, and when the current temperature is in the
dead zone, set 1, otherwise set 0.
Bit7: flag of frost alarm When the actual temperature is below 5
℃
, set 1, otherwise set 0. This bit is only as alert
signs, has no effect on the temperature control.
18
Output RHCC status
Temperature
control
2 byte
C, R, T
22.101 DPT_StatusRHCC
RHCC Status Report
Bit no: 0: error
,
“1” alarm
,
“0” normal
8: heating or cooling, "0" cooling, "1" heating
12: Dewpoint alarm, "1" alarm, "0": normal
13: frost alarm, "1" alarm, "0": normal
14: over-heat/cold alarm "1" alarm, "0": normal
Over-heat: the current temperature exceed 35
℃
, Over-cooling: the current temperature below 15
℃
19/20
/24/2
5
Basic/ heating/cooling control
value
Additional heating/cooling
control value
Temperature
control
1bit
1byte
C, R, T
1.001 DPT_Switch
5.001 DPT_Scaling
This communication object is used to send the control value of heating /cooling, to control actuator ON/OFF, and
adjust the room temperature.
Send telegrams
(
two position control――1bit
):
on/off
Send telegrams
(
two position control ――1byte
)
:
0%/100%
Send telegrams
(
continuous PI control
)
:
0…100%
Send telegrams
(
switching PI control
)
:
on/off
Send telegrams
(
switching PI control
)
:
on/off