GVS K-BUS
○
R
KNX/EIB
Thermostat
www.video-star.com.cn
marketing@video-star.com.cn
Tel.
:
(
8620
)
39338986
Fax.
:(
8620
)
39338465
88
This object sends a scene number by operating the switch, short press to call the scene, and long press to save the
current scene. The "scene number" is set in parameter "Number of scene".
Set an 8bit instruction(binary coded)
:
FXNNNNNN
F: “0 "-- call the scene;" 1 "--save the scene;
X
:
Undecided, no application
NNNNNN
:
scene number (0…63).
In parameter "Number of scene", scene number is 1~64, and the communication object "Number of light scene” sends
scene number 0~63. E.g. in parameter "Number of scene", scene number is 1, and the communication object "Number of
light scene” sends scene number 0.
55/58/61
Disable input 1/2/3
CH A/B/C Disable
1 bit
C,W
1.001 DPT_Switch
As above.
5.6.5
"Temperature limiter (underfloor heating)" Communication Object
Figure 5.6.5 NTC communication object
Number
Object name
Functions
Data types
Flags
DPT
54
Floor temperature
External temperature sensor
2 byte
C, T
9.001 DPT_Value_Temp
This communication object is used to send the current floor temperature.
Floor temperature sending variation refers to
parameter "Send temperature at variation of (
℃
)", the floor temperature cyclically sending refers to parameter
"period of sending temperature".
5.7 "Air Condition" Communication Object