The following three parameters are visible when selecting an external temperature sensor:
:
——Parameter“When external sensor fault, Internal sensor display”
The parameter annotation is in the external sensor Read when the temperature is not answered, the external
sensor is considered to be faulty, at which time the temperature is measured by the built-in sensor.
——Parameter“Time period for requesting external sensor [0..255]*1min”
This parameter is used to set the time period for the screen to send a read request to an external
temperature sensor. Options:0...255
——Parameter“Read external sensor after restart”
Available options:
NO
YES
NO
:
When the bus reset or programming is completed, the read request will not occur immediately, but wait
until the cycle time to send.
YES
:
After the bus is reset or programmed, a read request is sent to the external temperature sensor.
Parameter“Object type of fan speed”
This parameter is used to set the data type of wind speed. Available options:
:
1bit
1byte
Output value for fan speed
——Parameter“Output value for fan speed low/medium/high”
These three parameters are visible when the wind speed object type is "1byte", and define the values that
are sent to each wind speed. Options:0..255
Status feedback for fan speed
——Parameter“Status value for fan speed low/medium/high”
The three parameters are visible when the wind speed object type is "1byte", and the state feedback value of
each wind speed is set. The screen will be updated to show the wind speed according to the feedback value.
Options:0..255
Parameter“Operating mode switchover”
This parameter sets the object type of the room operation mode switch. Available options:
4x1bit
1byte
When you select 1bit ,4 1bit objects are visible. Four objects are:HVAC output--comfortmode (Comfort mode),
HVAC output--nightmode (Night mode), HVAC Output--standbyMode (Standby mode) and HVAC
output--frost/heat protectionmode.