Parameter “Floor status after bus recovery”
This parameter is used to set the Floor Status after bus recovery. Options:
No action
On
Off
Before bus power off *
If “Off” is selected, the Icon window are no operable, expect “Timing”, “On” and “Off”; If “On” is selected, the
Icon window is operable, the Radiant Floor Heating will do 2 Point operation according to Set Value and real
temperature to determine whether the Heating is On or Off.
NOTE:
The Function Before bus power off does not support restore the state before power off currently.
Parameter“Default set temperature[10..80]*0.5
℃
”
This parameter is used to set the initial temperature while the Heating is On. Options: 10..80
(
5~40
℃
)
Parameter“The value of object “Heating on/off””
The value of object “Heating on/off”. Options:
Heat on=1, Heat off=0
Heat on=0, Heat off=1
Parameter “Temperature control method”
The temperature control is via 2-Point Control.
While the real temperature is higher than Setting Value, the heating is Off, while below the setting value, the
heating is On.
Parameter “Hysteresis[0..200]*0.1
℃
”
This parameter is used to set the hysteresis of Set Value. Options: 0..100
While the real temperature is higher than setting temperature, the heating is off; while the temperature is
below or equal to the setting temperature-hysteresis, the heating is on.
Parameter “Min. /Man. set temperature [16..32]
℃
”
This parameter is used to limit the adjustable range of temperature settings. The Minimum value should
below the Maximum value.
It will sent as Limit value while the temperature setting value exceeds the limit range.
Parameter “Scene function”
This parameter is used to enable the Scene function of Heating, total 5 Scenes optional. Options:
Disable
Enable
——Parameter “x->Assign scene NO. (1..64,0 is inactive), x=1~5”
This parameter is used to set the scene number. Options: 0..64,0=inactive