K-BUS
KNX/EIB 3.5/5.0/10.1 inch Touch Panel Plus
58
○
R
Figure 6.4_11 “Px
:
Auto. control” Parameter Setting Windows
Parameter “Auto. Operation on object value”
This parameter is used to set the telegram value for activating the Auto. Operation. Options:
0=Auto/1=Cancel
1=Auto/0=Cancel
0=Auto/1=Cancel: Auto. Operation is activated when the object "Automatic function, In/Out" receiving the
telegram value "0".
When receiving "1", the Auto. Operation exit;
1=Auto/0=Cancel: Auto. Operation is activated when the object "Automatic function, In/Out" receiving the
telegram value "1".
When receiving "0", the Auto. Operation exit.
After bus voltage recovery or reset, Auto. Operation is not activated by default.
Parameter “Control value reference from”
This parameter is used to set the Control value reference from of Auto. Operation. Options:
PM2.5 (ug/m3)
CO2 (ppm)
Parameter “Period for request control value [0..255]*1min”
This parameter is used to set the period for request control value to external sensor. Options: 0...255
Parameter “The speed status when the control value error”
This parameter is used to set the speed status when the control value error. Options:
Off
Low
Medium
High
Tip:
When reading the control value from an external sensor, if there is no response, the external
sensor is faulty by default, the control value error.