K-BUS
KNX/EIB 3.5/5.0/10.1 inch Touch Panel Plus
82
○
R
7.3.4 “Air Quality display”Communication Object
Table 7.3_4 “Air Quality display”Communication Object
SN
Function
Communication Object Name Type
Attribute
DPT
5
AQI
Page x-Air Quality
2byte
C,W,T,U
7.001 pulses
The communication object is used to receive input value of AQI, acquire corresponding value from
the BUS and update to display. Range: 0~500
6
PM2.5
Page x-Air Quality
2byte
C,W,T,U
7.001 pulses
The communication object is used to receive input value of PM2.5, acquire corresponding value from
the BUS and update to display. The unit is ug/m
3
. Range: 0~999ug/m
3.
7
PM10
Page x-Air Quality
2byte
C,W,T,U
7.001 pulses
The communication is used to receive input value of PM10, acquiring corresponding value from the
BUS and updating to display. The unit is ug/m
3
. Range: 0~999ug/m
3.
8
Temperature
Page x-Air Quality
2Byte
C,W,T,U
9.001 temperature
The communication object is used to receive temperature measurement value sent by the
temperature sensor from the BUS. Range: -40~40
℃
.
9
Humidity
Page x-Air Quality
2byte
C,W,T,U
9.007 humidity
The communication object is used to receive humidity measurement value sent by the humidity
sensor from the BUS. Range: 0~100%
10
VOC
Page x-Air Quality
2byte
C,W,T,U
The communication object is used to receive input value of VOC, acquiring corresponding value from
the BUS and updating to display. The unit is mg/m
3
. Range: 0~9.99mg/m
3.
The object uses a non-standard data type, and the value is reduced based on the data point type
7.001 pulses. For example, the received value is 500, and the actual display value is 5.00 mg/m3.
11
CO2
Page x-Air Quality
2byte
C,W,T,U
9.008
DPT_Value_AirQuality
The communication object is used to receive input value of CO2, acquiring corresponding value from
the BUS and updating to display. The unit is ppm. The range: 0~4000ppm.
Table 7.3_4“Air Quality display”Communication Object Table