Parameter“z->Output y trigger scene NO. is(1~64,0=inactive)” (z:1~8)
This parameter is used to set the scene No.,which can trigger the output y.It support maximum 8 scenes of
each output.The options:
参
0..64
,
0=disable.
数
“Object value of output y (0..1/0..255/0..65535)”
The range of output value is determined by the datatype of output y. 1bit 0..1/1byte 0..255/ 2byte 0..65535
Parameter" Delay time for sending [0...255]*0.1s "
This parameter is used to set the delay time for sending to the bus.The options: 0..255
6.8 Parameter setting window“Logic function setting”
“Logic function”parameter setting window is shown in Fig.6.8_1,it is used to enable the Logic function and at
most 8 logic functions can be used.
Fig 6.8_1 “Logic function -- disable/enable”parameter setting window
Parameter“Function of channel”
This parameter is used to set the logic function of the channel.The options:
AND
OR
XOR
Gate forwarding
Threshold comparator
Format convert
As the parameter is similar to telecommunication object(only the logic algorithm is different),so we just
choose one of them to explain.