Splitting up loads  

Each relay can switch up to 120A depending on the voltage of the load. If the total current exceeds this 
120A, it may be possible to split up the load in multiple smaller loads. If it is possible to split up the load 
into smaller <120A loads, both relays on the SmartRelay or even multiple SmartRelays can be used. 
 

Example

  

An application has a nominal voltage of 24V, the total load is 200A. Connected are a two inverters, both 
100A. One inverter is used for the sockets, water kettle and lightning, the other inverter for the water 
heater (2000W). 
 

Do not connect both poles of relay1 to the poles of relay2 trying to “increase the maximum current”. 

Contacts in relays will never close at exactly the same time. Thus the total current will always be 
switched on or off in one relay. 

 
 
 
 
 