Testing PLC Systems
LT51 User Manual
19
4. Testing PLC Systems
Figure 4.1: Test Setup
– PLC Testing with LT51
1. Connect a coaxial cable between the BNC Adaptor (plugged into the LT51
RTXa-b terminals) and the RF coaxial interface of the PLC system unit.
2. Press the key, follow
ed by the [f2] “Meas Settings” soft-key. Press the
[f2] “Reset LT51” soft-key.
3. Press the button, then the [f1] soft-key to set
ZRTX
to "75 Ω", HiZ.
4. Press [f3] "RxRange" soft-key, and turn the knob to set the range to "0dB".
5. Connect the RF signal to the LT51 RTXab terminals
USING the 40dB
attenuator
.
VOICE
DATA
Fc1
Carrier
AF/VF
input
600 Ω
RF output
75 Ω
terminated
Fc2
Carrier
PLC
-40 dB
Attenuator
+40 dB
Supplied
Accessory