3-6
Step1
Remove the screw from the grounding hole on the switch chassis.
Step2
Put the supplied OT terminal of the PGND cable on the grounding screw.
Step3
Insert the grounding screw into the grounding hole and screw it down.
Step4
Connect the other end of the PGND cable to the grounding strip of the cabinet.
Figure 3-6
Connect the PGND cable
(1) Grounding hole
(2) Grounding screw
(3) PGND cable
Connection in Other Grounding Environments
Following are some methods for grounding the switch in different grounding environments that you are
likely to encounter when installing the switch at different places.
z
When a grounding strip is available at the installation site, attach one end of the yellow-green
PGND cable of the switch to the grounding screw on the grounding strip and fasten the grounding
screw.
The fire main and the lightning rod of the building are not good grounding options. The PGND cable of
the switch should be connected to the earthing system of the equipment room.