23
Figure 21
Rack depth
•
The rack is available with standard slide rails (or rack shelves), cage nuts, and screws.
•
The slide rails (or rack shelves) can support the weight of the switch chassis and its accessories.
•
The rack can be well grounded.
•
The rack has good cooling system, and the porosity of the front and back doors is greater than
50%.
Installation tools
You can use the following tools for installation.
Accessories supplied by the switch
Item Quantity
Purpose
Console cable
1
Connecting the console port and the configuration
terminal for switch login
Grounding cable
1
Grounding the switch
Mounting brackets
1 pair
Fixing the switch to the rack
M4*8 screw
1 set
Fixing the mounting brackets to the switch
M6*12 screw
1 set
Fixing the switch to the rack
M6 cage nut
1 set
Air deflector
1
Installed at the rear of the chassis to block air from
entering the chassis (optional for the S12508 and
S12518, not available for the S12504)
ESD-preventive wrist strap 2
ESD-prevention
>180
mm
>155
mm
>800
mm