2-13
Figure2-21 Attaching the mounting brackets and chassis rails to the S9826-32C switch
(power supply-side mounting position for the mounting brackets)
NOTE:
Secure the mounting brackets and chassis rails to both sides of the chassis in the same way.
Connecting the grounding cable to the chassis
CAUTION:
The primary grounding point and auxiliary grounding point are located on the left panel of the
chassis. You must connect the grounding cable to the grounding point before you mount the switch
in the rack.
This section uses the primary grounding point on the S9826-32C switch as an example.
To connect the grounding cable to a grounding point:
1.
Choose a grounding point as required.
This example uses the primary grounding point.
2.
Unpack the grounding cable and grounding screws.
3.
Use two grounding screws to attach the two-hole grounding lug of the grounding cable to the
grounding holes at the grounding point. Use a screwdriver to tighten the screws (recommended
torque: 20 kgf-cm). See
Figure2-22 Attaching the grounding cable to the primary grounding point on the S9826-32C
switch