2-14
Figure2-14 Attaching the mounting brackets and chassis rails to the
S9855-48CD8D/S9855-24B8DF switch (power supply-side mounting position for the
mounting brackets)
NOTE:
The mounting bracket and chassis rail installation procedures are the same for the left and right
chassis side panels.
Connecting the grounding cable to the switch
IMPORTANT:
As a best practice, use a torque of 20 kgf-cm (1.96 Nm) to fasten the grounding screws.
Connecting the grounding cable for the S9825-64D switch
The S9825-64D switch has one grounding point on the rear panel. S9825-64D switches with the
LS-9825-64D and LS-9825-64D-H1 product codes have the same grounding cable connection
method. The following uses an S9825-64D switch with the LS-9825-64D product code as an
example.
To connect the grounding cable to the S9825-64D switch:
1.
Unpack the grounding cable and grounding screws.
2.
Use the grounding screws to attach the two-hole grounding lug of the grounding cable to the
grounding holes at the grounding point. Then use a screwdriver to fasten the screws. See