11
2.
Place the firewall upside down on the workbench and clean the four round holes in the chassis
bottom with a dry cloth.
3.
Attach the four rubber feet to the round holes in the chassis bottom.
4.
Place the firewall with upside up on the workbench.
Figure2-2 Mounting the firewall on a workbench
Installing the firewall in a standard 19-inch rack
WARNING!
To avoid bodily injury and device damage, use a minimum of two persons to rack-mount the firewall.
CAUTION:
For adequate heat dissipation, ensure a minimum clearance of 80 mm (3.15 in) around the air inlet
and outlet vents of the chassis and a distance of 1U (44.45 mm, or 1.75 in) between the chassis and
other devices in the rack.
Rack-mounting the firewall by using front mounting brackets
The F1000-AI-05 and F1000-AI-15 firewalls support this installation method.
To install the firewall in a standard 19-inch rack by using front mounting brackets:
1.
Wear an ESD wrist strap and make sure the wrist strap makes good skin contact and is reliably
grounded.
2.
Unpack the firewall and accessories.
3.
Mark the cage nut installation positions on the rack posts by using the mounting brackets.
4.
Install cage nuts.