2-3
Device dimensions
Rack requirements
management bracket at the chassis front
25.5 mm (1.00 in) for the power module
handle at the chassis rear
front rack posts to the rear door.
•
518 mm (20.39 in) to 858 mm (33.78 in) from the
front rack posts to the rear rack posts.
To install the device in a standard 19-inch rack:
1.
Wear an ESD wrist strap and make sure the wrist strap makes good skin contact and is reliably
grounded.
2.
Unpack the device and accessories.
3.
Use a mounting bracket and a slide rail to mark the cage nut installation positions on the front
and rear rack posts, respectively. Four cage nuts are required on each front rack post and two
are required on each rear rack post.
4.
Install cages nuts at the marked positions.
5.
Use M6 screws to attach two slide rails to the rear rack posts.
Figure2-2 Installing cage nuts and slide rails
6.
Use the provided M4 screws to attach the mounting brackets and chassis rails to both sides of
the device.
The device provides multiple installation positions for chassis rails. Install chassis rails to the
appropriate positions and make sure the front ends of the slide rails can reach out of the chassis
rails after the device is installed in the rack.