6
•
The equipment room is at least 3 m (9.84 ft) high.
•
Reserve a minimum of 1 m (3.28 ft) of clearance between the rack and walls or other devices.
•
The dimensions of the rack are sufficient for the chassis. For more information about chassis
specifications, see "
Appendix A Chassis views and technical specifications
."
Table 5 Device dimensions and rack requirements
Model
Chassis dimensions
Rack requirements
M9006
•
Height
—353 mm (13.90 in)/8 RU
•
Width
—440 mm (17.32 in)
•
Depth
—757 mm (29.80 in)
{
660 mm (25.98 in) for the chassis
{
95 mm (3.74 in) for the cable
management bracket at the front of
the chassis
{
24 mm (0.94 in) for the switching
fabric module ejector levers at the
rear of the chassis
•
A minimum of 1.0 m
(3.28 ft) in depth
(recommended)
•
A minimum of 130 mm
(5.12 in) between the
front rack post and the
front door
•
A minimum of 690 mm
(27.17 in) between the
front rack post and the
rear door
M9010/M9010-GM
•
Height
—886 mm (34.88 in)/20 RU
•
Width
—440 mm (17.32 in)
•
Depth
—757 mm (29.80 in)
{
660 mm (25.98 in) for the chassis
{
95 mm (3.74 in) for the cable
management bracket at the front of
the chassis
{
24 mm (0.94 in) for the switching
fabric module ejector levers at the
rear of the chassis
M9014
•
Height
—797 mm (31.38 in)/18 RU
•
Width
—440 mm (17.32 in)
•
Depth
—757 mm (29.80 in)
{
660 mm (25.98 in) for the chassis
{
95 mm (3.74 in) for the cable
management bracket at the front of
the chassis
{
24 mm (0.94 in) for the switching
fabric module ejector levers at the
rear of the chassis
Installation tools
lists the tools and equipment that you might use during installation, and all of them are user
supplied. Prepare them before installation.
Table 6 Tools and equipment list
Category Tool
Measuring and
marking tools
Long tape, ruler (of 1 meter, or 3.28 ft), gradienter, marker, chalk line, and pencil
Drills
Hammer drill, electric drill, and several auxiliary drill bits