background image

Manual version: 6PW107-20210319 

BOM: 3123A0R2

 

ii 

Item Specification 

Compatible device models and 
slots 

 

M9010 gateway (slots 10 to 13) 

 

M9010-GM gateway (slots 10 and 11) 

 

T9010 IPS (slots 10 to 13) 

 

 

IMPORTANT: 

  You can configure a maximum of two switching fabric module for an M9010-GM gateway. 

  An M9010 gateway and a T9010 IPS each require a minimum of three switching fabric modules, 

and slots 10 and 11 must be installed with switching fabric modules. 

 

3  LEDs 

The module provides LEDs to show its operating status. 

Table 2 LED description 

RUN LED 

ALM LED 

Description 

Flashing (0.5 Hz)

Off 

The switching fabric module is operating properly. 

Off 

On 

The switching fabric module is faulty. 

Flashing (0.5 Hz)

On 

The temperature of the switching fabric module has exceeded the 
upper or lower limit. 

Off 

Off 

The switching fabric module has not started. 

On 

Off 

The switching fabric module is starting up. 

 

4  Installing and removing the module 

 

CAUTION: 

  Wear a well-grounded ESD-preventive wrist strap before you install or remove the module. 

  When you install or remove the module, avoid touching the components on it. 

 

4.1  

Installing the module 

1. 

Face the rear panel of the device. 

2. 

Remove the filler panel from the target slot. 

This example uses slot 11. 

3. 

Place the module horizontally with the component side facing up. Open the ejector levers and 
gently push the module into the slot along the guide rails, as shown by callout 1 in 

Figure 3

4. 

Close the ejector levers. Make sure the module is in close contact with the backplane, as shown 
by callout 2 in 

Figure 3

5. 

Use a Phillips screwdriver to fasten the captive screws on the module, as shown by callout 3 
in 

Figure 3