2-4
Table 2-3 Harmful gas limits in an equipment room
Gas
Maximum concentration (mg/m
3
)
SO
2
0.2
H
2
S 0.006
NO
2
0.04
NH
3
0.05
Cl
2
0.01
Grounding requirements
Correctly connecting the server grounding cable is crucial to lightning protection, anti-interference,
and ESD prevention.
The server can be grounded through the grounding wire of the power supply system and no external
grounding cable is required.