Grounding and lightning protection 

Table 8 

Grounding and lightning protection requirements 

Item 

Requirements 

Grounding 
resistance

 

 

The grounding resistance is typically required to 

be less than 5 ohms, and less than 10 ohms in an 

area that has less than 20 thunderstorm days a 

year. If an angle iron is to be buried into the 

earth as the earthing conductor, the grounding 

resistance is required to be less than 10 ohms. If 

the installation site has a high earth resistance 

rate, it is recommended to spray some salt water 

or resistance-reducing agent on the earth 

around the buried earthing conductor to 
reduce the resistance rate of the earth.  

 

The top of the earthing conductor should be at 

least 0.7 m (2.30 ft) away from the ground 

surface. In cold areas, the earthing conductor 
should be buried below the frozen soil layer. 

 

Protection 
grounding

 

 

If a grounding strip is available at the site, attach 

the yellow-green PGND cable of the AP to the 

grounding strip. The PGND cable must have a 

cross-section area of at least 6 mm

2

 (0.01 in

2

and a length not longer than 3 m (9.84 ft).  

 

If no grounding strip is available at the site, 

hammer a 0.5 m (1.64 ft) or longer angle iron or 

steel tube into the earth. The angle iron should 

be sized at least 50 × 50 × 5 mm (1.97 × 1.97 × 

0.20 in.); the steel tube should have a wall 

thickness of at least than 3.5 mm (0.18 in.) and 

be zinc-plated. Weld the yellow-green 

grounding cable to the angel iron or steel tube 

and treat the joint for corrosion protection. With 

a cross-section area of at least 6 mm

2

 (0.01 in

2

), 

the grounding cable should be as short as 
possible. Do not coil the cable. 

 

Make sure the lightning arresters of all devices 

and the peering devices connected to these 
devices are well grounded. 

 

Grounding 
lead

 

The grounding lead is a metal conductor 
connecting the grounding strip to the 
grounding grid. The PGND cable of the device 
should be attached to the grounding strip. The 
grounding lead should not be longer than 30 
m (98.43 ft). H3C recommends a zinc-plated 
flat steel with a cross-section area of 40 × 4 mm 
(1.57 × 0.16 in) or 50 × 5 mm (1.97 × 0.20 in).. 
The grounding strip and the grounding lead 
should be jointed using a 35 mm2 yellow-green 
PGND cable or directly welded together with 
the joint treated for corrosion protection. 

 

Summary of Contents for WA2600 Series

Page 1: ...Enhanced Series WLAN Access Points Installation Guide Abstract This document details the installation procedure for the WA2600 series enhanced WLAN access points Hangzhou H3C Technologies Co Ltd http...

Page 2: ...express or implied Hangzhou H3C Technologies Co Ltd and its licensors shall not be liable for technical or editorial errors or omissions contained herein Acknowledgments H3C Aolynk H3Care TOP G IRF Ne...

Page 3: ...13 3 Installing the AP 15 Determining the installation position 15 Installing the AP on a wall 15 Installing the wall mounting bracket on the wall 15 Installing the AP on the wall mounting bracket 17...

Page 4: ...iii Document conventions and symbols 23 Conventions 23 Symbols 24...

Page 5: ...perate with wireless local area network WLAN switches or access controllers to provide wireless access for WLAN users Figure 1shows a typical scenario of hotspot deployments using the WA2600 enhanced...

Page 6: ...configuration The two models of the WA2600 enhanced series have different radio frequencies RFs and structures For supported protocols and chassis material see Table 2 Table 2 Supported protocols and...

Page 7: ...Green 1 Displays the wireless link status On The wireless link is normal Off The wireless link is not initialized or the link is faulty Blinking slowly The wireless link works normally Blinking rapidl...

Page 8: ...Ethernet interface is in the link down state Blinking Data is being transmitted or received at 10 100 Mbps 1000M Ethernet interface LED Green 1 Displays the status of the 1000 M Ethernet interface On...

Page 9: ...terface Standards and protocols Description WA2610E AGN ANT 1 ANT 2 ANT 3 IEEE802 11a IEEE802 11b IEEE802 11g IEEE802 11n The antenna interfaces are provided for 2 4 GHz 5 GHz dual RF antennas for MIM...

Page 10: ...his antenna interface is used on a 2 4 GHz antenna or a feeder Antenna interface 5 G IEEE802 11a IEEE802 11n This antenna interface is used on a 5 GHz antenna or a feeder Console RS EIA 232 The consol...

Page 11: ...fore installation and operation Unpacking and inspection Before unpacking the product ensure that the package is not damaged and that it does not show signs of water damage When unpacking the package...

Page 12: ...Auxiliary tools Ladder and rubber hammer Installation site examination Before installation examine the installation site from the following aspects temperature and humidity requirements power supply a...

Page 13: ...48V 0 52A min Connect the adapter s power jack to the AP power interface If you need an AC DC power adapter for your H3C WA2600 series access point you must use the FSP025 1AD207A adapter part number...

Page 14: ...01 in2 and a length not longer than 3 m 9 84 ft If no grounding strip is available at the site hammer a 0 5 m 1 64 ft or longer angle iron or steel tube into the earth The angle iron should be sized...

Page 15: ...o the same earthing conductor Feeder The antenna support is ready and in accordance with the design requirement A feeder lightning rod is already installed and grounded according to the design require...

Page 16: ...eiling mounting Reinforce the ceiling if needed A padlock is required for ceiling mounting to prevent falloff due to shock or vibration Installing the AP on a wall This section describes how to instal...

Page 17: ...ey are all flush with the wall surface 3 Align the holes in the wall mounting bracket with the anchors and insert screws through the installation holes into the anchors as shown in Figure 8 Position t...

Page 18: ...E The installation procedure is the same for both the WA2610E AGN and WA2620E AGN The WA2610E AGN is used as an example in this guide 1 Align the AP with the hooks on the wall mounting bracket and han...

Page 19: ...the wall mounting bracket 1 Insert the locking plate into the security slot on the top of the AP see 1 in Figure 10 2 Turn the locking plate counterclockwise until the hole on the locking plate is al...

Page 20: ...19 Figure 10 Lock the AP onto the wall bracket Locking plate Latch Locking hole Wall mounting bracket Security slot 1 2 3...

Page 21: ...ice see Figure 12 Figure 12 PoE connection CAUTION In the PoE mode you do not need to connect the power interface to a power source You only need to connect one end of an Ethernet cable to the Etherne...

Page 22: ...enhanced series can access the Internet or metropolitan area network MAN through the Ethernet uplink interface Connect the Ethernet interface of the AP to an Ethernet interface of an Ethernet switch...

Page 23: ...s detailed configuration procedures and configuration examples for the H3C WX Series ACs A feature matrix and a command matrix are provided in Feature Matrix H3C WX Series Access Controllers Command R...

Page 24: ...dresses Blue underlined text http www hp com Website addresses Bold text Keys that are pressed Text entered into a GUI element such as a box GUI elements that are clicked or selected such as menu and...

Page 25: ...esult in bodily harm or death CAUTION Indicates that failure to follow directions could result in damage to equipment or data IMPORTANT Provides clarifying information or specific instructions NOTE Pr...

Reviews: