When using a home ventilation system including a fireplace,
it’s
obligatory to consult your responsible chimney sweeper!
For the fresh air supply connection on the stove, use a designated
insulated flexible pipe with a diameter of 60mm. If using rectangular tubes,
the appropriate cross section must be observed.
To prevent condensation, the air duct must be insulated and protected
from the wind.
To ensure the proper operation of the air inlet, shut-off equipments such
as throttles, valves, sliders must not be installed into the fresh air supply.
Also the outdoor suction piece has to be protected from blockages by a
protective grid.
There must be no vacuum in the installation area. When using
airconditioning systems such as ventilation systems, extractor hoods,
conveyors etc., the relevant technical rules and regulations must be
respected. Please contact your respectible chimney sweeper and
ventilation manufacturer.
The responsible chimney sweeper conducts an annual review of the
cross-section based on their regulations to make sure it is clean, safe
and operates properly. To this, appropriate inspection holes have to be
provided. Please turn to your local chimney sweeper on this subject.
Connection examples:
Air supply from below
max. tubing length 4m
Air supply from behind
max. tubing length 4m
Air supply from above
Only with certified
chimney system