background image

 

5.2.  Combustion air supply 

  It must be ensured that there is sufficient fresh air at the place of installation.  

 

5.3.  Outside air connection 

 We recommend using the outside air connection for the supply of combustion air in order not to use up the 

valuable indoor air when heating.  
 

 

To do this, connect the air intake elbow located on the back to a hose or a similar, suitable air duct or to a 
chimney system designed for this purpose. The diameter of the air duct must be at least the diameter of 
the outdoor air connection on the stove. 

 

The end of the air duct must be located outside or in a well ventilated area (basement).  

 It is not recommended to feed the cold air into the room from outside via a direct duct, as this can lead to the 

build-up of condensation. 
 

 

In order to  guarantee  a sufficient supply  of air, the duct should not be longer than approx. 3 m and  not 
have too many bends.  

 

If the duct leads outside, it must end with a 90° bend facing down or a wind protection device (see Figure 
4). 

 

 

Figure 4:

 

Wind protection of air supply duct

 

 

For  operation  independent  of  indoor  air  with  RLU  certified  appliances,  the  outside  air  connection  must  be 

connected.  

 

For the dimensions of the air supply duct: 

Air supply duct diameter  Maximum length 

Max. number of 90° 
bends 

50mm 

0.5 m 

100mm 

3 m 

 

 

If the dimensions are lower than specified, then it is not possible to operate the fireplace properly and it will lead 

to increased contamination of the burner and inspection window.

 

Summary of Contents for HSP 6 PALLAZZA-III 519.08

Page 1: ...PELLET STOVE Nameplate Aufstellungs und Bedienungsanleitung Pelletofen DE Fiche descritive Poele FR Schema tecnica strufa Camino IT Equipment sheet Fireplace GB Tshnicki podaci Kaminsku HR Podatkovni...

Page 2: ...8 2 Energy saving mode ACTUAL room temperature display 9 8 3 Button lock child safety device 9 9 Functions in the main menu 9 9 1 Main menu Select functions 9 9 1 1 Operating mode Week program Settin...

Page 3: ...tricted covered or shut off On stoves with an outdoor air connection the opening must not be shut or closed during operation Make children aware of these dangers and keep them away from the fireplace...

Page 4: ...flue tube does not stick out into the open cross section of the chimney which would interfere with the flue gases rising and prevent the optimal cleaning of the chimney The use of wall lagging is rec...

Page 5: ...recommended to feed the cold air into the room from outside via a direct duct as this can lead to the build up of condensation In order to guarantee a sufficient supply of air the duct should not be l...

Page 6: ...iameter Identification DINplus Norm M 7135 ENplus A1 7 2 Unsuitable fuels The use of lower quality or unauthorised fuel adversely affects the operation of your pellet stove and may lead to the lapse o...

Page 7: ...its mounting Close the combustion chamber door Fill the storage container with pellets Plug in mains cable Tip Only when using for the first time place approx 30 pellets in the burner This speeds up t...

Page 8: ...er until it reaches the necessary flame temperature and only then switches to the cooling operating status and then OFF During the first use odours may build up for a short time Please ensure that the...

Page 9: ...ctivation Hold the Menu button down for approx 10 seconds until Button block activated no longer appears on the display 9 Functions in the main menu 9 1 Main menu Select functions OK language english...

Page 10: ...tch on time can now be set with the Plus or Minus buttons The switch off time on the respective week day can be programmed by pressing the right hand arrow button The required room temperature is sele...

Page 11: ...with the Plus or Minus buttons The setting is saved by pressing the OK button To exit the function press the On Off button 9 1 4 Heating curve How it works h003 OK 2 2 main menu heating curve set fac...

Page 12: ...given on the WLAN module operating instructions 9 1 7 Fill manually Optional only on HSP8 on screw conveyor off main menu Fill manually Procedure Place the cursor in the main menu on Fill manually Pr...

Page 13: ...the START of the respective test setting 10 Operating statuses 10 1 Start Zone 1 20 Start phase The start phase begins if the current room temperature falls below the set target temperature by 1 C the...

Page 14: ...CO mode Eco mode means continuous operation at a low output if the ACTUAL room temperature is higher than the set TARGET room temperature i e the stove does not switch off but continues to run on a sm...

Page 15: ...p battery so that data is retained during a power cut A distinction is made between a short power cut and a long power cut Short power cut The short cut lasts for less than about 30 seconds Once the e...

Page 16: ...tive G Pellet fuel has too low a calorific value A Clean burner B Clean burner fill pellet tank C Clean the intake on the screw conveyor housing with a vacuum cleaner Clean burner D Clean burner Ensur...

Page 17: ...alorific value E Downpipe screw conveyor blocked F Room too airtight required combustion air cannot flow into the room G Flame temperature sensor defective H Screw motor defective A Fill pellet tank B...

Page 18: ...eals seals of any kind handles invalidate a warranty Maintenance or cleaning not performed or performed inadequately a flue draft that is incorrectly set to the appliance or is insufficient or too hig...

Reviews: