background image

14 

Problem 

Reason 

Solution 

Effect of weather between the seasons. 

See Chapter 11.5. “Operation between the 
seasons”. 

Primary air limiter (PAL) is dirty, blocking the 
pendulum flap. 

Clean primary air limiter (PAL)(see Chapter 
12.3.). 

Primary air limiter (PAL) is incorrectly installed, 
blocking the pendulum flap. 

Correctly install primary air limiter (PAL) (see 
chapter 12.3.). 

The seals on the burner (on fire chamber door, 
electric ignition bar, cooking plate, pressure 
equalisation plate) are defective. 

Replace seals. 

Pressure equalisation plate is not supported 
properly. 

Carefully place the pressure equalization plate. 

With electric ignition the ignition bar on the burner 
is not sealed or only insufficiently so. 

Carefully seal the ignition bar. 

Incorrect fuel is used for heating. 

Use only  Extra light fuel oil (ELFO) (see Chapter 
11.1.). 

 

Remove soot deposits with the help of a soot 
removing agent (e.g. Wunderblitz soot removing 
agent). 

Stove cannot be 
ignited, 

No oil supply to 
the burner 

 

Oil tank or living room tank is empty. 

Fill up oil tank or living room tank. 

Defect in the central oil supply. 

Look for cause of problem in the central oil 
supply. 

Controller latch on oil controller clogs oil supply. 

Lift controller latch (see Chapter 11.3.). 

Clogged oil filter. 

Clean filter (see Chapter 12.2). 

Oil inlet in burner insert clogged. 

Operate cleaning crank (see Chapter 12.1.). 

Water in the oil controller and/or in the oil line. 

Completely empty oil controller and clean (see 
Chapter 12.2.), disconnect oil lines between oil 
controller and burner and drain. 

Tank shut-off valve is closed. 

Open valve. 

Quick closing valve with central oil supply is 
closed. 

Open valve. 

The liquid oil stove igniter does not work with new 
stove. 

Use wax strip or paraffin-saturated wick. 

 

The oil stove heat 
output is 
insufficient 

The output controller is set too low. 

Set output controller higher. 

The stove is not installed horizontally. 

Align oil stove with water level. 

The delivery pressure (chimney draught) is too low.  Clarify with chimney-sweeper. 

 

The oil stove heat 
output is 
excessive 

The seals on the burner (on fire chamber door, 
electric ignition bar, pressure equalisation plate) 
are defective. 

Replace seals. 

Pressure equalisation plate is not supported 
properly. 

Carefully position pressure equalisation plate. 

The output controller is set too high. 

Set output controller lower 

The delivery pressure (chimney draught) is too 
high. 

Clarify with chimney-sweeper. 

View window 
pane quickly 
covered with soot 

 

Imperative: every glass window must be cleaned 
from time to time after use, see Chapter 12.4. 
“Cleaning the appliance surfaces”. 

The delivery pressure (chimney draught ) is too 
low. 

Clarify with chimney-sweeper. 

 

Operate the oven for starting as described in 
Chapter 12.4. “Igniting and normal operation” . 

Stove has a 
strong smell or 
smokes on the 
outside 

Burning-in phase of the protective varnish or stove 
is dirty/dusty. 

Complete burning-in phase and clean the outside 
of the stove when cold. 

Oil lines leaking. 

Seal loose screw connections by carefully 
tightening the union nuts (without force). 

When filling the tank oil was spilt or the tank was 
overfilled. 

See Chapter 12.2. “Filling the oil tank”. 

Defect in the 
electrical ignition 

Ignition bar is defective. 

Replace ignition bar (see Chapter 12.5.). 

Microfuse is blown. 

Renew microfuse (see Chapter 12.5.). 

Electrical contact on the bimetal switch fails to 
close. 

Turn adjusting screw on the bimetal switch 1 to 2 
turns in a clockwise direction  (see Figure 17). 

Defect on the fork toggle switch on the oil 
controller. 

Have the fork toggle switch replaced by technical 
personnel. 

Defect in the socket, supply cable or fuse. 

Request electrician to check the fuses. 

Ignition bar produces insufficient heat output 
because of poor electrical contact on the ignition 
bar. 

Secure cable mounting screws on the ignition bar 
(see Chapter 12.5.). 

Ignition bar produces inadequate heat output 
because ignition transformer is defective. 

Have the ignition transformer replaced by 
technical personnel. 

Stove burns with 
loud noise 

Primary air limiter fails to work properly. 

Maintain the primary air limiter (see Chapter 
12.3). 

Delivery pressure is too high. 

Clarify with chimney-sweeper, see Chapter 11. 

Summary of Contents for Ibiza 469.50

Page 1: ...t stoves Tiled and slow burning stoves for wood and coal Slow burning and auxiliary stoves for wood coal and oil Fireplace inserts for wood Electric fireplaces Accessories for stove and fireplace Accessories for central oil supply Air humidifiers Haas Sohn Sales in Germany Ofentechnik GmbH Haas Sohn Ofentechnik GmbH Urstein Nord 67 Zur Dornheck 8 A 5412 Puch D 35764 Sinn eMail office haassohn com ...

Page 2: ...or safe operation and for possibly occurring faults and their remedy In order to comply with the Appliance Safety Act these operating instructions must therefore be accessible to the user of the appliance at all times Keep these instructions therefore in a safe place We can provide warranty on our products only if you comply with the following guidelines of these installation and operating instruc...

Page 3: ...tove unobstructed even during the operation of exhaust systems bathroom exhaust fans kitchen extractors etc in your home or in any other connected rooms Stove operation is not jeopardized when the systems only circulate the air within a room or the systems are equipped with safety installations that automatically and reliably prevent vacuum in the installation room It is imperative that you should...

Page 4: ... 181072 181072 181072 18 Control linkage 181059 181059 181059 19 Öil controller 182036 182036 182036 20 Oil inlet spigot with cleaning crank 173137 173137 173137 21 Oil line oil controller burner 181073 181073 182974 22 Tank insert lid 127221 127221 127221 23 Tank strainer 127211 127211 127211 24 Oil level gauge floating ball 127230 127230 127230 27 Fire chamber door 182569 181348 182514 28 Oil gu...

Page 5: ... room tank Article No 1 straight ferrule screw connection 8x8 102151 1 flexible fuel oil hose 50cm 75 cm 100 cm 104212 104213 104214 1 pressure controller 8x8 105170 1 oil pump z B 100280 1 quick closing valve 105146 Additional accessories angular ferrule screw connections T ferrule screw connections reducing screw connections oil flow meter filter change over valves etc are always available from ...

Page 6: ...right of the flue pipe spigot are located in the rear wall of the stove corresponding with the holes of the tank bracket Insert 4 snap on clips see Figures 5 6 either in the 4 left or right slits L or R 4 Now hook the tank bracket into the top and bottom snap on clips see Figure 7 Figure 7 Installing the tank bracket 1 Tank bracket 2 Rear wall 3 Snap on clip Figure 8 Assembly of the insert angles ...

Page 7: ...To do so remove the prepared opening in the rear wall by breaking out the sheet metal and insert the oil guide plate see Figure 2 6 A For emptying or cleaning the oil pan can be removed either from the front or from the rear Figure 11 Ibiza 469 50 Installation of oil guide plate 1 Oil guide plate 2 Recess 3 Rear wall 8 Conversion instructions for the model Viking 468 50 to vertical flue pipe conne...

Page 8: ...lue pipe does not protrude into the free cross section of the chimney see Figure 13 To insert the pipe in the chimney the use of wall lining is recommended Flue pipe connections of neighbouring rooms must be connected to the chimney with at least a 50 cm stagger see figure 13 Wrong With longer flue gas pipe configuration maximum 3 m horizontal sections must be avoided piping that rises in the dire...

Page 9: ...oned above such as petrol benzene engine lubricating oil waste oil or solvents must never be burnt in your heating appliance Neither should you use any additives or other additional substances with your fuel oil Notes 1 Store fuel oil only in tanks intended for this purpose and in suitable storage rooms while observing the regulations of your responsible fire protection authority or building autho...

Page 10: ... the lever will drop automatically This will enable the oil to flow from the oil tank or from the central oil supply to the oil controller Figure 20 Oil controller 1 Control pin 2 Safety lever controller latch 3 Oil drain plug 4 Filter cover with seal When igniting during initial start up oil controller and lines must first be allowed to fill with oil This takes approximately 3 minutes With each s...

Page 11: ...into the burner is not damaged Otherwise the electric ignition function will be detrimentally affected For some maintenance operations you will have to remove the inspection panel the rear wall Viking or sidewall Ibiza see Figures 1 2 On model Viking 468 50 it is only required to lift the inspection panel see Figure 1 below the fire chamber door a few millimetres before unhooking possible without ...

Page 12: ...n either the tank shut off valve or with central oil supply the quick closing valve Remove water in the heating appliance as follows 1 Drain oil from the oil controller by opening the drain plug and the filter cover 2 Unscrew connection line from the oil controller to the burner open end wrench 14 and 17 and drain When installing the oil line ensure that the screw connections are tightened careful...

Page 13: ...crews of the retaining plate see figure 24 and remove the retaining plate with a short anti clockwise movement 4 Pull the ignition bar from the burner by lightly turning 90 5 It is imperative to secure the glass fibre seal approximately 2 3 mm diameter see Figure 24 around the new ignition bar to completely seal the hole 6 Place the tension spring on the ignition bar 7 Install the ignition bar in ...

Page 14: ...chimney sweeper The oil stove heat output is excessive The seals on the burner on fire chamber door electric ignition bar pressure equalisation plate are defective Replace seals Pressure equalisation plate is not supported properly Carefully position pressure equalisation plate The output controller is set too high Set output controller lower The delivery pressure chimney draught is too high Clari...

Page 15: ...onnection of the appliance insufficient or excessive chimney draft incorrectly performed repair work or other especially subsequent changes to the fireplace or flue gas line stove pipe and chimney failure to observe the installation and operating instructions as well as installation of spare parts and accessories not included in our lists use of unsuitable or contaminated fuels admixing corrosion ...

Page 16: ...instructions Our tip Transfer the data from the nameplate of the stove in Figure 24 If no remark concerning model and manufacturing numbers is provided on page 1 of these instructions please enter them there In this way you will always have immediate access to all important data H A A S S O H N Ofentechnik GmbH Herborner Straße 7 9 35764 Sinn MODEL NUMBER MANUFACTURING NO RATED HEAT OUTPUT W DIN R...

Reviews: