14
Installation
Figure 7
Attaching the Digital Gateway using the Quick-connect Fittings
3.2.1.2 Hard-wiring the Digital Gateway to the sc100
Important Note: Hard-wiring the digital gateway to the sc100 is not an approved method
for Class 1, Division 2 Hazardous Locations.
1.
Disconnect power to the controller if powered.
2.
Open the controller cover.
3.
Disconnect and remove the existing wires between the quick-connect and terminal
strip J5, see
Figure 8 on page 15
.
4.
Remove the quick-connect fitting and wires and install the threaded plug on the
opening to maintain the environmental rating.
5.
Cut the connector from the sensor cable.
6.
Strip the insulation on the cable back 1-inch. Strip ¼-inch of each individual wire end.
Note: Use of strain relief fitting other than Cat. No. 16664 may result in a hazard. Use only the
recommended strain relief fitting.
7.
Pass the cable through conduit and a conduit hub or a strain relief fitting (Cat. No.
16664) and an available access hole in the controller enclosure. Tighten the fitting.
8.
Reinstall the plug on the sensor access opening to maintain the environmental rating.
9.
Wire as shown in
Table 4
and
Figure 8
.
10. Close and secure the cover.
Summary of Contents for 6120118
Page 2: ...Visit us at www hach com...
Page 6: ...Visit us at www hach com...
Page 10: ...Visit us at www hach com...
Page 18: ...Visit us at www hach com...
Page 32: ...Visit us at www hach com...
Page 36: ...Visit us at www hach com...
Page 38: ...Visit us at www hach com...
Page 42: ...Visit us at www hach com...
Page 50: ...Visit us at www hach com...
Page 52: ...Visit us at www hach com...