OPERATING
Disable Mode is used to disable or isolate individual zone circuits or all sounder circuits, all auxiliary
outputs and any delays to outputs.
To initialise Disable Mode firstly activate the controls by turning
the key switch or by entering the four digit code. Then press and
hold the Disable Mode button (1) for 3 seconds.
After 3 seconds the panel will bleep and the General Disablement
LED and Zone 1 Fault LED will pulse slowly, indicating that Zone
1 is in disable selection mode.
Pressing the Disable Mode button again will move disable selection mode to Zone 2 and the Zone 2 Fault
LED will be pulsing instead. Subsequent presses will move the selection to Zones 3 - 12, dependant on
the number of zones fitted to the panel. I.e up to zone 4 on a 4 zone, 6 on a 6 zone, 8 on a 8 zone etc.
After the last available zone the next press will move the selection mode to the sounder circuits, indicated
by the Sounder Status LED and then to the Aux outputs, indicated by the Aux Output Status LED and
finally to the Delay LED. Pressing the button once more will move the selection back to Zone 1 again.
When the desired circuit, outputs or delays to be disabled is indicated
by a slow pulsing LED, use the ENTER button to select it. Once selected
the indicator LED will change to a rapid pulse. Pressing ENTER again will
toggle the circuit between disabled and enabled. Then use Disable Mode
button again to move to the next circuit. Any or all circuits, outputs or
delays can be disabled simultaneously.
When all disablements have been set, press and hold the Disable Mode
button for 3 seconds again. This will exit the disable selection mode and the panel will return to standby.
All disabled circuits and the General Disablement will now be indicated by a steady LED.
To enable the circuits again, repeat the above process using the Disable Mode button to select the circuit
and the ENTER button to remove the disablement.
Tip:
With the controls active, pressing the Disable Mode button briefly will reveal which circuits are disabled (as
opposed to in test mode). This is useful if using Disable Mode and Test Mode at the same time.
DISABLE MODE
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
Summary of Contents for ESENTO MARINE ESEN-R-12MAR
Page 24: ...www haes tech com ...