Esento-RDU Installation, Commissioning & Operating Manual
Approved Document Ref: DOC00636 Issue 4.0
2
ABOUT THIS PANEL
PRODUCT OVERVIEW
The Esento, LCD Remote Display repeater panels have the same, easy to use, controls and indications as
the main control panels with the addition of a 4 line x 40 character, backlit LCD display.
The remote display units are fully functional with ‘Silence’, ‘Resound’ and ‘Reset’ controls, as well as
Disable and Test Mode functions. It is also possible to disable the controls for each or all repeater panels
to make them passive (indication only). Up to 8 repeater panels can be supported on a system.
Repeater panels are designed to be wired in a fault tolerant (fail safe) loop configuration, from comms A
to B and back to the main panel again. This enables repeater panels to still work if there is a break in the
cables.
If replacing an older system where the existing cabling cannot be configured in a loop as above, it is
possible to re-programme the control panel back to legacy RS485 circuit comms monitoring. This then
allows any topology of comms cabling to be utilised.
The main circuit board has 2, switch –ve, outputs which provide fire and fault signals. Inputs are available
for use as PSU fault inputs. An input for a remote key-switch is also provided.
Controls are enabled via a 4 digit code entry. The user code can be changed in the programming settings.
An eight button keypad is used to control the system and allow access to the function options.
The remote display unit is housed in a robust sheet steel enclosure suitable for wall mounting. Cable entry
is via 20mm ‘knockouts’ located at the top and rear of the cabinet.
A nominal 28v dc supply is required to power the remote display units which can be obtained from the
control panel or remote power supply unit.
Quiesecent and alarm current details for standby battery calculations
Standby Current
Alarm Current
XL-RDU remote display unit
60mA
89mA