ESPRIT Gas Extinguishing User Manual
OPERATING INSTRUCTIONS
30
Approved Document Ref: UI-ESG-01 Issue 2.0
Status LED Indicators
LED Name
LED ON
LED PULSING
Zones in Fire 1 - 3
N/A
Indicates alarm condition in
zone.
Zone Fault/Test/Disabled/ 1 -
3
Indicates a zone circuit is
disabled or in test mode.
Indicates a fault in the zone
circuit.
Supply Healthy:
Indicates mains and/or battery
supply is present.
N/A
General Fire:
Panel in alarm condition and
alarms silenced
Indicates panel is in alarm
condition
General Fault:
Indicates Fault has been
acknowledged (Mute Buzzer
button pressed)
Indicates Disablement present
(Disablement LED illuminated)
Indicates one or more faults are
present
Disablement:
Indicates one or more circuits
have been disabled.
N/A
Test Mode:
Indicates one or more circuits
are in test mode
N/A
Sounder Status:
Indicates sounder circuits have
been disabled or are in test
mode
Indicates a fault on one or more
sounder circuits.
Power Supply Fault:
N/A
Indicates a power supply fault
on mains power input or battery
Delay Status:
Delays are configured
Delay is running
System Fault:
Indicates a system failure, panel
not functional or the internal
PCB configuration has not been
set up correctly
Indicates the panel has
recovered from a system fault.
Release Imminent
Signal to release extinguishant
has been activated.
Indicates that the release of
extinguishant is imminent.
Gas Released
N/A
Indicates that the release of
extinguishant has occurred and
the panel has detected the flow
of the extinguishant released
Low pressure
Indicates low pressure circuit is
disabled or in test mode.
Indicates that the extinguishant
cylinder has lost pressure and
requires attention
Timer Held
Indicates that the imminent
release of extinguishant is
temporarily suspended
Indicates a fault in the Hold off
circuit