ESPRIT Gas Extinguishing User Manual
CONFIGURING THE PANEL
41
Approved Document Ref: UI-ESG-01 Issue 2.0
CONFIGURING THE PANEL
When the system is installed and is ready to be commissioned, configuring the system consists of:
•
Use the
CONFIG PANEL
menu
LEARN
option - On initial commissioning; or following removal
or addition of external device(s) (sounder, call point, detector, etc.), set the system to
automatically learn what internal cards, external devices and RSUs are connected.
•
Set Common Output for HOLD and ABORT
–
On initial commissioning; or following removal
or addition of sounders, set any of the outputs for use as a common output indication, to show
activation of HOLD and ABORT functions.
•
Panel Setup (
User
menu)
–
Set Auto/Manual Modes, Display brightness, Internal Buzzer
volume, system Time and Date, etc.
•
Device Outputs (
CONFIG
Menu)
–
Set configuration options for the panel (sounder options,
reset password, set inhibit time, reset panel defaults, etc.), internal cards (timer options, etc.),
External Devices (device names, output options, etc.).
•
Extinguishant release (
CONTROL
Menu)
–
Set configurable options for extinguishant release,
including for FLOOD and EXTRACT.
Accessing the Menu Structure
Power-on the panel and wait for it to perform a routine status check. Any faults detected will be
displayed, accompanied by a warning tone. Press the
Mute Buzzer
button to silence the warning tone.
Resolve any faults before proceeding.
Next proceed by pressing the
✓
button, the LCD unit displays the following Access Level 2 Menu (see
picture below):
To access the menu structure:
•
Turn
Activate Controls
key switch clockwise to
On
or
•
use the keypad to enter Authorised User (Access level 2) code
1111
:
•
Press
✓
key to select Access level 2. The digital display will show the following message:
Enter Level 2 Access Code
o
Use Up/Down arrow keys to increase/decrease the number value
o
Use Left/Right arrow keys to move to the next digit in the 4-digit sequence
o
When all 4 digits have been set to the code
1111
, press the
✓
key again
o
The LCD unit displays the Access Level 2
Main Menu
(see picture below), which is
available for operation
Note:
Access level 2 Menu will deactivate after 30 sec if not used.
www.acornfiresecurity.com
www.acornfiresecurity.com